Systems

Systems are modeled with the system marker tag. Systems the logical structure of buildings meant to group multiple equip that serve a similar purpose. The members of a system do not necessarily have to be in the same physical space. For example, a Chilled Water System may consist of equipment within the Chilled Water Plant, but also Air Handlers with Chilled Water Coils fed by that plant. Systems do not represent a physical structure unless also paired with an equip tag (e.g., if system is used in conjunction with a plant-equip).

Tags

System entities should define a siteRef tag for their parent tag. All systems subtype from system and are then kebab cased with other valid tags to create the conjunct (e.g., chilled-water-system).

It is also valid for systems to define a systemRef tag to describe a sub-system or primary/secondary relationship. This relationship would imply logical containment, i.e., all members of a sub-system automatically belong to the referent system as well.

Examples

Here are examples of a properly tagged system and member equipment:

//chilled water system for a building
id: @chwSys
dis: “Chilled Water System”
chilled
water
system
siteRef: @site


//condenser water system for a building
id: @cwSys
dis: “Condenser Water System”
condenser
water
system
siteRef: @site


//chilled water plant
id: @chwPlant
dis: “Chilled Water Plant”
chilled
water
plant
equip
siteRef: @site
systemRef: @chwSys


//condenser water plant
id: @cwPlant
dis: “Condenser Water Plant”
condenser
water
plant
equip
siteRef: @site
systemRef: @cwSys


//water cooled chiller, co-membership in both systems
id: @chiller
dis: “Chiller ##”
chiller
equip
siteRef: @site
systemRef: [@chwSys, @cwSys]
equipRef: @chwPlant
chilledWaterRef: @chwPlant
condenserWaterRef: @cwPlant


//heat exchanger, co-membership in both systems
id: @hx
dis: “Heat Exchanger ##”
heatExchanger
equip
siteRef: @site
systemRef: [@chwSys, @cwSys]
equipRef: @chwPlant
chilledWaterRef: @chwPlant
condenserWaterRef: @cwPlant


//chilled water pump
id: @chwp
dis: “Chilled Water Pump ##"
chilled
water
pump
motor
equip
siteRef: @site
systemRef: [@chwSys, @cwSys]
equipRef: @chwPlant
chilledWaterRef: @chwPlant
condenserWaterRef: @cwPlant


//condenser water pump
id: @chwp
dis: “Chilled Water Pump ##"
chilled
water
pump
motor
equip
siteRef: @site
systemRef: [@chwSys, @cwSys]
equipRef: @chwPlant
chilledWaterRef: @chwPlant
condenserWaterRef: @cwPlant