@prefix rdf: . @prefix rdfs: . @prefix xsd: . @prefix owl: . @prefix ph: . @prefix phScience: . @prefix phIoT: . ph:hasTag a owl:ObjectProperty ; rdfs:range ph:marker . _:b-0000 a phIoT:site ; ph:hasTag phIoT:site ; rdfs:label "Bravo" ; phIoT:area 78000 ; ph:dis "Bravo" ; ph:geoAddr "123 Some Rd, Fort Wayne, IN 46900" ; ph:geoCity "Fort Wayne" ; ph:geoCountry "US" ; ph:geoCounty "US" ; ph:geoPostalCode "46900" ; ph:geoState "IN" ; ph:geoStreet "123 Some Rd" ; phIoT:primaryFunction "Hospital (General Medical & Surgical)" ; ph:tz "Chicago" ; phIoT:weatherStationRef _:b-042f ; phIoT:yearBuilt 2000 ; _:custom _:0ae0983b-e2fa-1940-c772-f23c91a70cca . _:0ae0983b-e2fa-1940-c772-f23c91a70cca rdfs:label "" ; _:elecFreq 60 . _:b-0001 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-1" ; ph:dis "Bravo BCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0ae0983b-e2fa-1941-c773-f23c91a70cca . _:0ae0983b-e2fa-1941-c773-f23c91a70cca rdfs:label "" . _:b-0002 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-1 Cooling Valve Output" ; ph:dis "Bravo BCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e2fa-1942-c774-f23c91a70cca . _:0ae0983b-e2fa-1942-c774-f23c91a70cca rdfs:label "" ; _:predictionConf 0.31259757180034364 ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0003 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-1 Mixed Air Damper Output" ; ph:dis "Bravo BCU-1 Mixed Air Damper Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e2fa-1943-c775-f23c91a70cca . _:0ae0983b-e2fa-1943-c775-f23c91a70cca rdfs:label "" ; _:predictionConf 0.28394372966813813 ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0004 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-1 Supply Air Temperature" ; ph:dis "Bravo BCU-1 Supply Air Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e2fa-1944-c776-f23c91a70cca . _:0ae0983b-e2fa-1944-c776-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7893816782198223 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0005 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature" ; ph:dis "Bravo BCU-1 Zone Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e2fa-1945-c777-f23c91a70cca . _:0ae0983b-e2fa-1945-c777-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6720981954640639 ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0006 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e2fa-1946-c778-f23c91a70cca . _:0ae0983b-e2fa-1946-c778-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0007 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-2" ; ph:dis "Bravo BCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0ae0983b-e309-5b80-c779-f23c91a70cca . _:0ae0983b-e309-5b80-c779-f23c91a70cca rdfs:label "" . _:b-0008 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-2 Cooling Valve Output" ; ph:dis "Bravo BCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e309-5b81-c77a-f23c91a70cca . _:0ae0983b-e309-5b81-c77a-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0009 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-2 Mixed Air Damper Output" ; ph:dis "Bravo BCU-2 Mixed Air Damper Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e309-5b82-c77b-f23c91a70cca . _:0ae0983b-e309-5b82-c77b-f23c91a70cca rdfs:label "" ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-000a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-2 Supply Air Temperature" ; ph:dis "Bravo BCU-2 Supply Air Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b83-c77c-f23c91a70cca . _:0ae0983b-e309-5b83-c77c-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature" ; ph:dis "Bravo BCU-2 Zone Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b84-c77d-f23c91a70cca . _:0ae0983b-e309-5b84-c77d-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-000c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b85-c77e-f23c91a70cca . _:0ae0983b-e309-5b85-c77e-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000d a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo BCUs" ; ph:dis "Bravo BCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e309-5b86-c77f-f23c91a70cca . _:0ae0983b-e309-5b86-c77f-f23c91a70cca rdfs:label "" . _:b-000e a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 1" ; ph:dis "Bravo Boiler 1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0ae0983b-e309-5b87-c780-f23c91a70cca . _:0ae0983b-e309-5b87-c780-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-000f a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 1 Boiler Status" ; ph:dis "Bravo Boiler 1 Boiler Status" ; phIoT:equipRef _:b-000e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e309-5b88-c781-f23c91a70cca . _:0ae0983b-e309-5b88-c781-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr1Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0010 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 2" ; ph:dis "Bravo Boiler 2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0ae0983b-e309-5b89-c782-f23c91a70cca . _:0ae0983b-e309-5b89-c782-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-0011 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 2 Boiler Status" ; ph:dis "Bravo Boiler 2 Boiler Status" ; phIoT:equipRef _:b-0010 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e309-5b8a-c783-f23c91a70cca . _:0ae0983b-e309-5b8a-c783-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr2Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0012 a phIoT:hot-water-plant ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Boiler Plant" ; ph:dis "Bravo Boiler Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-0013 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:domestic, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; ph:dis "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b8b-c784-f23c91a70cca . _:0ae0983b-e309-5b8b-c784-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwSp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0014 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:delta, phIoT:his, phIoT:hot, phIoT:point, phScience:pressure, phIoT:sp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; ph:dis "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0ae0983b-e309-5b8c-c785-f23c91a70cca . _:0ae0983b-e309-5b8c-c785-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0015 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heating, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Return Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Return Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b8d-c786-f23c91a70cca . _:0ae0983b-e309-5b8d-c786-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0016 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e309-5b8e-c787-f23c91a70cca . _:0ae0983b-e309-5b8e-c787-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWSTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0017 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo CHW System" ; ph:dis "Bravo CHW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e309-5b8f-c788-f23c91a70cca . _:0ae0983b-e309-5b8f-c788-f23c91a70cca rdfs:label "" . _:b-0018 a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-1" ; ph:dis "Bravo CHWP-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-0019 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-0018 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e309-5b90-c789-f23c91a70cca . _:0ae0983b-e309-5b90-c789-f23c91a70cca rdfs:label "" ; _:poinTags "point and chilled and water and cmd and pump" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-001a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-0018 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e309-5b91-c78a-f23c91a70cca . _:0ae0983b-e309-5b91-c78a-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-14T01:00:03.512-04:00"^^xsd:dateTime ; _:precision 2 ; _:dataSyncType "error" . _:b-001b a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-2" ; ph:dis "Bravo CHWP-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-001b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e318-9dc0-c78b-f23c91a70cca . _:0ae0983b-e318-9dc0-c78b-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-001d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-001b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e318-9dc1-c78c-f23c91a70cca . _:0ae0983b-e318-9dc1-c78c-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-001e a phIoT:chilled-water-plant ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Chilled Water Plant" ; ph:dis "Bravo Chilled Water Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cooling, phIoT:cur, phIoT:enable, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Cooling Enable" ; ph:dis "Bravo Chilled Water Plant AHU Cooling Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e318-9dc2-c78d-f23c91a70cca . _:0ae0983b-e318-9dc2-c78d-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUClgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0020 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:heating, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Heating Enable" ; ph:dis "Bravo Chilled Water Plant AHU Heating Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e318-9dc3-c78e-f23c91a70cca . _:0ae0983b-e318-9dc3-c78e-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUHtgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0021 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; ph:dis "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e318-9dc4-c78f-f23c91a70cca . _:0ae0983b-e318-9dc4-c78f-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0022 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:bypass, phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; ph:dis "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e318-9dc5-c790-f23c91a70cca . _:0ae0983b-e318-9dc5-c790-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0023 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-3 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-3 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e318-9dc6-c791-f23c91a70cca . _:0ae0983b-e318-9dc6-c791-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0024 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-4 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-4 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e346-6480-c792-f23c91a70cca . _:0ae0983b-e346-6480-c792-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0025 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0ae0983b-e346-6481-c793-f23c91a70cca . _:0ae0983b-e346-6481-c793-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0026 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:primaryLoop, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0ae0983b-e346-6482-c794-f23c91a70cca . _:0ae0983b-e346-6482-c794-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3397244142906628 ; _:sourcePointName "ChwDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0027 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6c0-c795-f23c91a70cca . _:0ae0983b-e355-a6c0-c795-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "CHWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0028 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6c1-c796-f23c91a70cca . _:0ae0983b-e355-a6c1-c796-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "ChwsTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0029 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6c2-c797-f23c91a70cca . _:0ae0983b-e355-a6c2-c797-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-002a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chilled Water Plant Chiller Status" ; ph:dis "Bravo Chilled Water Plant Chiller Status" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6c3-c798-f23c91a70cca . _:0ae0983b-e355-a6c3-c798-f23c91a70cca rdfs:label "" ; _:predictionConf 0.15013386549340826 ; _:sourcePointName "RunSTATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-002b a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "kW/ton" ; _:custom _:0ae0983b-e355-a6c4-c799-f23c91a70cca . _:0ae0983b-e355-a6c4-c799-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-002c a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0ae0983b-e355-a6c5-c79a-f23c91a70cca . _:0ae0983b-e355-a6c5-c79a-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-002d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6c6-c79b-f23c91a70cca . _:0ae0983b-e355-a6c6-c79b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH1_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-002e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6c7-c79c-f23c91a70cca . _:0ae0983b-e355-a6c7-c79c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH1_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-002f a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6c8-c79d-f23c91a70cca . _:0ae0983b-e355-a6c8-c79d-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0030 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chiller 1 Setpoint" ; ph:dis "Bravo Chiller 1 Chiller 1 Setpoint" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6c9-c79e-f23c91a70cca . _:0ae0983b-e355-a6c9-c79e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH1_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0031 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 1 Chiller Act. Capacity" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e355-a6ca-c79f-f23c91a70cca . _:0ae0983b-e355-a6ca-c79f-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0032 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 1 Chiller Enable" ; ph:dis "Bravo Chiller 1 Chiller Enable" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6cb-c7a0-f23c91a70cca . _:0ae0983b-e355-a6cb-c7a0-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH1_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0033 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Status" ; ph:dis "Bravo Chiller 1 Chiller Status" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6cc-c7a1-f23c91a70cca . _:0ae0983b-e355-a6cc-c7a1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH1_ChlrSts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0034 a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0ae0983b-e355-a6cd-c7a2-f23c91a70cca . _:0ae0983b-e355-a6cd-c7a2-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-0035 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6ce-c7a3-f23c91a70cca . _:0ae0983b-e355-a6ce-c7a3-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH2_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0036 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e355-a6cf-c7a4-f23c91a70cca . _:0ae0983b-e355-a6cf-c7a4-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH2_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0037 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e355-a6d0-c7a5-f23c91a70cca . _:0ae0983b-e355-a6d0-c7a5-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0038 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chiller 2 Setpoint" ; ph:dis "Bravo Chiller 2 Chiller 2 Setpoint" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e364-e900-c7a6-f23c91a70cca . _:0ae0983b-e364-e900-c7a6-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH2_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0039 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 2 Chiller Act. Capacity" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e364-e901-c7a7-f23c91a70cca . _:0ae0983b-e364-e901-c7a7-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-003a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 2 Chiller Enable" ; ph:dis "Bravo Chiller 2 Chiller Enable" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e902-c7a8-f23c91a70cca . _:0ae0983b-e364-e902-c7a8-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH2_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-003b a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Status" ; ph:dis "Bravo Chiller 2 Chiller Status" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e903-c7a9-f23c91a70cca . _:0ae0983b-e364-e903-c7a9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH2_ChlrSts" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-003c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-1" ; ph:dis "Bravo EF-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-003d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-1 Exhaust Fan Enable" ; ph:dis "Bravo EF-1 Exhaust Fan Enable" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e904-c7aa-f23c91a70cca . _:0ae0983b-e364-e904-c7aa-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-003e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-1 Exhaust Fan Status" ; ph:dis "Bravo EF-1 Exhaust Fan Status" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e905-c7ab-f23c91a70cca . _:0ae0983b-e364-e905-c7ab-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-003f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-10" ; ph:dis "Bravo EF-10" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0040 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-10 Exhaust Fan Enable" ; ph:dis "Bravo EF-10 Exhaust Fan Enable" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e906-c7ac-f23c91a70cca . _:0ae0983b-e364-e906-c7ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0041 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-10 Exhaust Fan Status" ; ph:dis "Bravo EF-10 Exhaust Fan Status" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e907-c7ad-f23c91a70cca . _:0ae0983b-e364-e907-c7ad-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-06-23T01:00:04.326-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0042 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-11" ; ph:dis "Bravo EF-11" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0043 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-11 Exhaust Fan Enable" ; ph:dis "Bravo EF-11 Exhaust Fan Enable" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e908-c7ae-f23c91a70cca . _:0ae0983b-e364-e908-c7ae-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0044 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-11 Exhaust Fan Status" ; ph:dis "Bravo EF-11 Exhaust Fan Status" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e909-c7af-f23c91a70cca . _:0ae0983b-e364-e909-c7af-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0045 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-12" ; ph:dis "Bravo EF-12" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0046 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-12 Exhaust Fan Enable" ; ph:dis "Bravo EF-12 Exhaust Fan Enable" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90a-c7b0-f23c91a70cca . _:0ae0983b-e364-e90a-c7b0-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0047 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-12 Exhaust Fan Status" ; ph:dis "Bravo EF-12 Exhaust Fan Status" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90b-c7b1-f23c91a70cca . _:0ae0983b-e364-e90b-c7b1-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0048 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-13" ; ph:dis "Bravo EF-13" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0049 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-13 Exhaust Fan Enable" ; ph:dis "Bravo EF-13 Exhaust Fan Enable" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90c-c7b2-f23c91a70cca . _:0ae0983b-e364-e90c-c7b2-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-13 Exhaust Fan Status" ; ph:dis "Bravo EF-13 Exhaust Fan Status" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90d-c7b3-f23c91a70cca . _:0ae0983b-e364-e90d-c7b3-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004b a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-14" ; ph:dis "Bravo EF-14" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-14 Exhaust Fan Enable" ; ph:dis "Bravo EF-14 Exhaust Fan Enable" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90e-c7b4-f23c91a70cca . _:0ae0983b-e364-e90e-c7b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-14 Exhaust Fan Status" ; ph:dis "Bravo EF-14 Exhaust Fan Status" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e90f-c7b5-f23c91a70cca . _:0ae0983b-e364-e90f-c7b5-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004e a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-15" ; ph:dis "Bravo EF-15" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-15 Exhaust Fan Enable" ; ph:dis "Bravo EF-15 Exhaust Fan Enable" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e364-e910-c7b6-f23c91a70cca . _:0ae0983b-e364-e910-c7b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0050 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-15 Exhaust Fan Status" ; ph:dis "Bravo EF-15 Exhaust Fan Status" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b40-c7b7-f23c91a70cca . _:0ae0983b-e374-2b40-c7b7-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0051 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-16" ; ph:dis "Bravo EF-16" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0052 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-16 Exhaust Fan Enable" ; ph:dis "Bravo EF-16 Exhaust Fan Enable" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b41-c7b8-f23c91a70cca . _:0ae0983b-e374-2b41-c7b8-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0053 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-16 Exhaust Fan Status" ; ph:dis "Bravo EF-16 Exhaust Fan Status" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b42-c7b9-f23c91a70cca . _:0ae0983b-e374-2b42-c7b9-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0054 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-17" ; ph:dis "Bravo EF-17" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0055 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-17 Exhaust Fan Enable" ; ph:dis "Bravo EF-17 Exhaust Fan Enable" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b43-c7ba-f23c91a70cca . _:0ae0983b-e374-2b43-c7ba-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0056 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-17 Exhaust Fan Status" ; ph:dis "Bravo EF-17 Exhaust Fan Status" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b44-c7bb-f23c91a70cca . _:0ae0983b-e374-2b44-c7bb-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0057 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-18" ; ph:dis "Bravo EF-18" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0058 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Enable" ; ph:dis "Bravo EF-18 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0057 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b45-c7bc-f23c91a70cca . _:0ae0983b-e374-2b45-c7bc-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0059 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Status" ; ph:dis "Bravo EF-18 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0057 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b46-c7bd-f23c91a70cca . _:0ae0983b-e374-2b46-c7bd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-005a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-19" ; ph:dis "Bravo EF-19" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Enable" ; ph:dis "Bravo EF-19 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-005a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b47-c7be-f23c91a70cca . _:0ae0983b-e374-2b47-c7be-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-005c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Status" ; ph:dis "Bravo EF-19 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-005a ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b48-c7bf-f23c91a70cca . _:0ae0983b-e374-2b48-c7bf-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-005d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-2" ; ph:dis "Bravo EF-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-2 Exhaust Fan Enable" ; ph:dis "Bravo EF-2 Exhaust Fan Enable" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b49-c7c0-f23c91a70cca . _:0ae0983b-e374-2b49-c7c0-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-005f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-2 Exhaust Fan Status" ; ph:dis "Bravo EF-2 Exhaust Fan Status" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4a-c7c1-f23c91a70cca . _:0ae0983b-e374-2b4a-c7c1-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0060 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-20" ; ph:dis "Bravo EF-20" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0061 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-20 Exhaust Fan Enable" ; ph:dis "Bravo EF-20 Exhaust Fan Enable" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4b-c7c2-f23c91a70cca . _:0ae0983b-e374-2b4b-c7c2-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0062 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-20 Exhaust Fan Status" ; ph:dis "Bravo EF-20 Exhaust Fan Status" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4c-c7c3-f23c91a70cca . _:0ae0983b-e374-2b4c-c7c3-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0063 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-21" ; ph:dis "Bravo EF-21" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0064 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Enable" ; ph:dis "Bravo EF-21 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0063 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4d-c7c4-f23c91a70cca . _:0ae0983b-e374-2b4d-c7c4-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0065 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Status" ; ph:dis "Bravo EF-21 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0063 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4e-c7c5-f23c91a70cca . _:0ae0983b-e374-2b4e-c7c5-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0066 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-22" ; ph:dis "Bravo EF-22" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0067 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Enable" ; ph:dis "Bravo EF-22 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0066 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e374-2b4f-c7c6-f23c91a70cca . _:0ae0983b-e374-2b4f-c7c6-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0068 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Status" ; ph:dis "Bravo EF-22 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0066 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e383-6d80-c7c7-f23c91a70cca . _:0ae0983b-e383-6d80-c7c7-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0069 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-23" ; ph:dis "Bravo EF-23" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-23 Exhaust Fan Enable" ; ph:dis "Bravo EF-23 Exhaust Fan Enable" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3440-c7c8-f23c91a70cca . _:0ae0983b-e3b1-3440-c7c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23SS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-006b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-23 Exhaust Fan Status" ; ph:dis "Bravo EF-23 Exhaust Fan Status" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3441-c7c9-f23c91a70cca . _:0ae0983b-e3b1-3441-c7c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23Status" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-24" ; ph:dis "Bravo EF-24" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-24 Exhaust Fan Enable" ; ph:dis "Bravo EF-24 Exhaust Fan Enable" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3442-c7ca-f23c91a70cca . _:0ae0983b-e3b1-3442-c7ca-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-24 Exhaust Fan Status" ; ph:dis "Bravo EF-24 Exhaust Fan Status" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3443-c7cb-f23c91a70cca . _:0ae0983b-e3b1-3443-c7cb-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-006f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-25" ; ph:dis "Bravo EF-25" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0070 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Enable" ; ph:dis "Bravo EF-25 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-006f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3444-c7cc-f23c91a70cca . _:0ae0983b-e3b1-3444-c7cc-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0071 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Status" ; ph:dis "Bravo EF-25 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-006f ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3445-c7cd-f23c91a70cca . _:0ae0983b-e3b1-3445-c7cd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0072 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-26" ; ph:dis "Bravo EF-26" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0073 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-26 Exhaust Fan Enable" ; ph:dis "Bravo EF-26 Exhaust Fan Enable" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3446-c7ce-f23c91a70cca . _:0ae0983b-e3b1-3446-c7ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0074 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-26 Exhaust Fan Status" ; ph:dis "Bravo EF-26 Exhaust Fan Status" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3b1-3447-c7cf-f23c91a70cca . _:0ae0983b-e3b1-3447-c7cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0075 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-27" ; ph:dis "Bravo EF-27" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0076 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-27 Exhaust Fan Enable" ; ph:dis "Bravo EF-27 Exhaust Fan Enable" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7680-c7d0-f23c91a70cca . _:0ae0983b-e3c0-7680-c7d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0077 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-27 Exhaust Fan Status" ; ph:dis "Bravo EF-27 Exhaust Fan Status" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7681-c7d1-f23c91a70cca . _:0ae0983b-e3c0-7681-c7d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0078 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-28" ; ph:dis "Bravo EF-28" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0079 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-28 Exhaust Fan Status" ; ph:dis "Bravo EF-28 Exhaust Fan Status" ; phIoT:equipRef _:b-0078 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7682-c7d2-f23c91a70cca . _:0ae0983b-e3c0-7682-c7d2-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF28Status" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-007a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-3" ; ph:dis "Bravo EF-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-3 Exhaust Fan Enable" ; ph:dis "Bravo EF-3 Exhaust Fan Enable" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7683-c7d3-f23c91a70cca . _:0ae0983b-e3c0-7683-c7d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-007c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-3 Exhaust Fan Status" ; ph:dis "Bravo EF-3 Exhaust Fan Status" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7684-c7d4-f23c91a70cca . _:0ae0983b-e3c0-7684-c7d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-007d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-4" ; ph:dis "Bravo EF-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-4 Exhaust Fan Enable" ; ph:dis "Bravo EF-4 Exhaust Fan Enable" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7685-c7d5-f23c91a70cca . _:0ae0983b-e3c0-7685-c7d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-007f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-4 Exhaust Fan Status" ; ph:dis "Bravo EF-4 Exhaust Fan Status" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7686-c7d6-f23c91a70cca . _:0ae0983b-e3c0-7686-c7d6-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0080 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-5" ; ph:dis "Bravo EF-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0081 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-5 Exhaust Fan Enable" ; ph:dis "Bravo EF-5 Exhaust Fan Enable" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7687-c7d7-f23c91a70cca . _:0ae0983b-e3c0-7687-c7d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0082 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-5 Exhaust Fan Status" ; ph:dis "Bravo EF-5 Exhaust Fan Status" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7688-c7d8-f23c91a70cca . _:0ae0983b-e3c0-7688-c7d8-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0083 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-6" ; ph:dis "Bravo EF-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0084 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-6 Exhaust Fan Enable" ; ph:dis "Bravo EF-6 Exhaust Fan Enable" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-7689-c7d9-f23c91a70cca . _:0ae0983b-e3c0-7689-c7d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0085 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-6 Exhaust Fan Status" ; ph:dis "Bravo EF-6 Exhaust Fan Status" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768a-c7da-f23c91a70cca . _:0ae0983b-e3c0-768a-c7da-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-05-28T01:00:09.102-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0086 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-7" ; ph:dis "Bravo EF-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0087 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-7 Exhaust Fan Enable" ; ph:dis "Bravo EF-7 Exhaust Fan Enable" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768b-c7db-f23c91a70cca . _:0ae0983b-e3c0-768b-c7db-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0088 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-7 Exhaust Fan Status" ; ph:dis "Bravo EF-7 Exhaust Fan Status" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768c-c7dc-f23c91a70cca . _:0ae0983b-e3c0-768c-c7dc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0089 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-8" ; ph:dis "Bravo EF-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-8 Exhaust Fan Enable" ; ph:dis "Bravo EF-8 Exhaust Fan Enable" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768d-c7dd-f23c91a70cca . _:0ae0983b-e3c0-768d-c7dd-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-008b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-8 Exhaust Fan Status" ; ph:dis "Bravo EF-8 Exhaust Fan Status" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768e-c7de-f23c91a70cca . _:0ae0983b-e3c0-768e-c7de-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-008c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-9" ; ph:dis "Bravo EF-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-9 Exhaust Fan Enable" ; ph:dis "Bravo EF-9 Exhaust Fan Enable" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3c0-768f-c7df-f23c91a70cca . _:0ae0983b-e3c0-768f-c7df-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-008e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-9 Exhaust Fan Status" ; ph:dis "Bravo EF-9 Exhaust Fan Status" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3cf-b8c0-c7e0-f23c91a70cca . _:0ae0983b-e3cf-b8c0-c7e0-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-02T01:00:04.305-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-008f a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0090 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-1 Cooling Valve Output" ; ph:dis "Bravo FCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8c1-c7e1-f23c91a70cca . _:0ae0983b-e3cf-b8c1-c7e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0091 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-1 Heating Valve Output" ; ph:dis "Bravo FCU-1 Heating Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8c2-c7e2-f23c91a70cca . _:0ae0983b-e3cf-b8c2-c7e2-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0092 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature" ; ph:dis "Bravo FCU-1 Zone Temperature" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8c3-c7e3-f23c91a70cca . _:0ae0983b-e3cf-b8c3-c7e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0093 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8c4-c7e4-f23c91a70cca . _:0ae0983b-e3cf-b8c4-c7e4-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0094 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0095 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-2 Cooling Valve Output" ; ph:dis "Bravo FCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8c5-c7e5-f23c91a70cca . _:0ae0983b-e3cf-b8c5-c7e5-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0096 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-2 Heating Valve Output" ; ph:dis "Bravo FCU-2 Heating Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8c6-c7e6-f23c91a70cca . _:0ae0983b-e3cf-b8c6-c7e6-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0097 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature" ; ph:dis "Bravo FCU-2 Zone Temperature" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8c7-c7e7-f23c91a70cca . _:0ae0983b-e3cf-b8c7-c7e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0098 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8c8-c7e8-f23c91a70cca . _:0ae0983b-e3cf-b8c8-c7e8-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0099 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-3" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-3 Cooling Valve Output" ; ph:dis "Bravo FCU-3 Cooling Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8c9-c7e9-f23c91a70cca . _:0ae0983b-e3cf-b8c9-c7e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-009b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-3 Heating Valve Output" ; ph:dis "Bravo FCU-3 Heating Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8ca-c7ea-f23c91a70cca . _:0ae0983b-e3cf-b8ca-c7ea-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature" ; ph:dis "Bravo FCU-3 Zone Temperature" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8cb-c7eb-f23c91a70cca . _:0ae0983b-e3cf-b8cb-c7eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-3 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8cc-c7ec-f23c91a70cca . _:0ae0983b-e3cf-b8cc-c7ec-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-009e a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-4" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-4 Cooling Valve Output" ; ph:dis "Bravo FCU-4 Cooling Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8cd-c7ed-f23c91a70cca . _:0ae0983b-e3cf-b8cd-c7ed-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-4 Heating Valve Output" ; ph:dis "Bravo FCU-4 Heating Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3cf-b8ce-c7ee-f23c91a70cca . _:0ae0983b-e3cf-b8ce-c7ee-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature" ; ph:dis "Bravo FCU-4 Zone Temperature" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3cf-b8cf-c7ef-f23c91a70cca . _:0ae0983b-e3cf-b8cf-c7ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-4 Zone Temperature Setpoint" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e3de-fb00-c7f0-f23c91a70cca . _:0ae0983b-e3de-fb00-c7f0-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a3 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo FCUs" ; ph:dis "Bravo FCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e3de-fb01-c7f1-f23c91a70cca . _:0ae0983b-e3de-fb01-c7f1-f23c91a70cca rdfs:label "" . _:b-00a4 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Fans" ; ph:dis "Bravo Fans" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e3de-fb02-c7f2-f23c91a70cca . _:0ae0983b-e3de-fb02-c7f2-f23c91a70cca rdfs:label "" . _:b-00a5 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 1" ; ph:dis "Bravo HHW Pump 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump Status" ; ph:dis "Bravo HHW Pump 1 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a5 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb03-c7f3-f23c91a70cca . _:0ae0983b-e3de-fb03-c7f3-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 1 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb04-c7f4-f23c91a70cca . _:0ae0983b-e3de-fb04-c7f4-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00a8 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 2" ; ph:dis "Bravo HHW Pump 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump Status" ; ph:dis "Bravo HHW Pump 2 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a8 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb05-c7f5-f23c91a70cca . _:0ae0983b-e3de-fb05-c7f5-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 2 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a8 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb06-c7f6-f23c91a70cca . _:0ae0983b-e3de-fb06-c7f6-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00ab a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo HW System" ; ph:dis "Bravo HW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e3de-fb07-c7f7-f23c91a70cca . _:0ae0983b-e3de-fb07-c7f7-f23c91a70cca rdfs:label "" . _:b-00ac a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-1" ; ph:dis "Bravo RTU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0ae0983b-e3de-fb08-c7f8-f23c91a70cca . _:0ae0983b-e3de-fb08-c7f8-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15300 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 145 ; _:designOutsideAirFlowMin 3500 ; _:designDischargeFanAirDeltaPressure 7.04 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59 ; _:designChilledWaterPower 722.3 ; _:designHotWaterFlow 24.1 ; _:designChilledWaterFlow 96.4 ; _:designReturnAirFlow 15300 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 15300 ; _:designReturnFanPower 15 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.66 . _:b-00ad a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 AHU Operation Mode" ; ph:dis "Bravo RTU-1 AHU Operation Mode" ; phIoT:equipRef _:b-00ac ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb09-c7f9-f23c91a70cca . _:0ae0983b-e3de-fb09-c7f9-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-1 Cooling Valve Output" ; ph:dis "Bravo RTU-1 Cooling Valve Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3de-fb0a-c7fa-f23c91a70cca . _:0ae0983b-e3de-fb0a-c7fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-1 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e3de-fb0b-c7fb-f23c91a70cca . _:0ae0983b-e3de-fb0b-c7fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-1 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e3de-fb0c-c7fc-f23c91a70cca . _:0ae0983b-e3de-fb0c-c7fc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00b1 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0ae0983b-e41c-0400-c7fd-f23c91a70cca . _:0ae0983b-e41c-0400-c7fd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-1 Humidifier Enable" ; ph:dis "Bravo RTU-1 Humidifier Enable" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e41c-0401-c7fe-f23c91a70cca . _:0ae0983b-e41c-0401-c7fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-1 Humidifier Output" ; ph:dis "Bravo RTU-1 Humidifier Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-0402-c7ff-f23c91a70cca . _:0ae0983b-e41c-0402-c7ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00b4 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-1 Max Damper Position" ; ph:dis "Bravo RTU-1 Max Damper Position" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-0403-c800-f23c91a70cca . _:0ae0983b-e41c-0403-c800-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-0404-c801-f23c91a70cca . _:0ae0983b-e41c-0404-c801-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-00b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e41c-0405-c802-f23c91a70cca . _:0ae0983b-e41c-0405-c802-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-0406-c803-f23c91a70cca . _:0ae0983b-e41c-0406-c803-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature" ; ph:dis "Bravo RTU-1 Mixed Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e41c-0407-c804-f23c91a70cca . _:0ae0983b-e41c-0407-c804-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e41c-0408-c805-f23c91a70cca . _:0ae0983b-e41c-0408-c805-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-1 Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-0409-c806-f23c91a70cca . _:0ae0983b-e41c-0409-c806-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Outside Air Flow" ; ph:dis "Bravo RTU-1 Outside Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e41c-040a-c807-f23c91a70cca . _:0ae0983b-e41c-040a-c807-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00bc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e41c-040b-c808-f23c91a70cca . _:0ae0983b-e41c-040b-c808-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.656-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00bd a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Percent Outside Air" ; ph:dis "Bravo RTU-1 Percent Outside Air" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-040c-c809-f23c91a70cca . _:0ae0983b-e41c-040c-c809-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Damper Output" ; ph:dis "Bravo RTU-1 Return Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e41c-040d-c80a-f23c91a70cca . _:0ae0983b-e41c-040d-c80a-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Flow" ; ph:dis "Bravo RTU-1 Return Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e41c-040e-c80b-f23c91a70cca . _:0ae0983b-e41c-040e-c80b-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Humidity" ; ph:dis "Bravo RTU-1 Return Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4640-c80c-f23c91a70cca . _:0ae0983b-e42b-4640-c80c-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-00c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Return Air Temperature" ; ph:dis "Bravo RTU-1 Return Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e42b-4641-c80d-f23c91a70cca . _:0ae0983b-e42b-4641-c80d-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Fan Status" ; ph:dis "Bravo RTU-1 Return Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e42b-4642-c80e-f23c91a70cca . _:0ae0983b-e42b-4642-c80e-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-1 Return Fan VFD Speed" ; ph:dis "Bravo RTU-1 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4643-c80f-f23c91a70cca . _:0ae0983b-e42b-4643-c80f-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Flow" ; ph:dis "Bravo RTU-1 Supply Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e42b-4644-c810-f23c91a70cca . _:0ae0983b-e42b-4644-c810-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Humidity" ; ph:dis "Bravo RTU-1 Supply Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4645-c811-f23c91a70cca . _:0ae0983b-e42b-4645-c811-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4646-c812-f23c91a70cca . _:0ae0983b-e42b-4646-c812-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e42b-4647-c813-f23c91a70cca . _:0ae0983b-e42b-4647-c813-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Static Pressure" ; ph:dis "Bravo RTU-1 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e42b-4648-c814-f23c91a70cca . _:0ae0983b-e42b-4648-c814-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature" ; ph:dis "Bravo RTU-1 Supply Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e42b-4649-c815-f23c91a70cca . _:0ae0983b-e42b-4649-c815-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e42b-464a-c816-f23c91a70cca . _:0ae0983b-e42b-464a-c816-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Fan Status" ; ph:dis "Bravo RTU-1 Supply Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e42b-464b-c817-f23c91a70cca . _:0ae0983b-e42b-464b-c817-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00cc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-1 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e42b-464c-c818-f23c91a70cca . _:0ae0983b-e42b-464c-c818-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00cd a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 VAV Total Flow" ; ph:dis "Bravo RTU-1 VAV Total Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e42b-464d-c819-f23c91a70cca . _:0ae0983b-e42b-464d-c819-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ce a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-2" ; ph:dis "Bravo RTU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0ae0983b-e42b-464e-c81a-f23c91a70cca . _:0ae0983b-e42b-464e-c81a-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 30000 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 288 ; _:designOutsideAirFlowMin 6750 ; _:designDischargeFanAirDeltaPressure 6.4 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59.2 ; _:designChilledWaterPower 1225.8 ; _:designHotWaterFlow 48 ; _:designChilledWaterFlow 160.9 ; _:designReturnAirFlow 30000 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 30000 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 50 ; _:designReturnFanAirDeltaPressure 1.62 . _:b-00cf a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 AHU Operation Mode" ; ph:dis "Bravo RTU-2 AHU Operation Mode" ; phIoT:equipRef _:b-00ce ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e42b-464f-c81b-f23c91a70cca . _:0ae0983b-e42b-464f-c81b-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4650-c81c-f23c91a70cca . _:0ae0983b-e42b-4650-c81c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3970116854281743 ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-2 Cooling Valve Output" ; ph:dis "Bravo RTU-2 Cooling Valve Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e42b-4651-c81d-f23c91a70cca . _:0ae0983b-e42b-4651-c81d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-2 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-8880-c81e-f23c91a70cca . _:0ae0983b-e43a-8880-c81e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d3 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-2 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e43a-8881-c81f-f23c91a70cca . _:0ae0983b-e43a-8881-c81f-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00d4 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0ae0983b-e43a-8882-c820-f23c91a70cca . _:0ae0983b-e43a-8882-c820-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-2 Humidifier Enable" ; ph:dis "Bravo RTU-2 Humidifier Enable" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e43a-8883-c821-f23c91a70cca . _:0ae0983b-e43a-8883-c821-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-2 Humidifier Output" ; ph:dis "Bravo RTU-2 Humidifier Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-8884-c822-f23c91a70cca . _:0ae0983b-e43a-8884-c822-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00d7 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-2 Max Damper Position" ; ph:dis "Bravo RTU-2 Max Damper Position" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-8885-c823-f23c91a70cca . _:0ae0983b-e43a-8885-c823-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-2 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e43a-8886-c824-f23c91a70cca . _:0ae0983b-e43a-8886-c824-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00d9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Min Outdoor Air Flow" ; ph:dis "Bravo RTU-2 Min Outdoor Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e43a-8887-c825-f23c91a70cca . _:0ae0983b-e43a-8887-c825-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:predictionConf 0.5591032698291575 ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-8888-c826-f23c91a70cca . _:0ae0983b-e43a-8888-c826-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature" ; ph:dis "Bravo RTU-2 Mixed Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e43a-8889-c827-f23c91a70cca . _:0ae0983b-e43a-8889-c827-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e43a-888a-c828-f23c91a70cca . _:0ae0983b-e43a-888a-c828-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-2 Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-888b-c829-f23c91a70cca . _:0ae0983b-e43a-888b-c829-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Outside Air Flow" ; ph:dis "Bravo RTU-2 Outside Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e43a-888c-c82a-f23c91a70cca . _:0ae0983b-e43a-888c-c82a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00df a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e43a-888d-c82b-f23c91a70cca . _:0ae0983b-e43a-888d-c82b-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00e0 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Percent Outside Air" ; ph:dis "Bravo RTU-2 Percent Outside Air" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-888e-c82c-f23c91a70cca . _:0ae0983b-e43a-888e-c82c-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00e1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Damper Output" ; ph:dis "Bravo RTU-2 Return Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-888f-c82d-f23c91a70cca . _:0ae0983b-e43a-888f-c82d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Flow" ; ph:dis "Bravo RTU-2 Return Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e43a-8890-c82e-f23c91a70cca . _:0ae0983b-e43a-8890-c82e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Humidity" ; ph:dis "Bravo RTU-2 Return Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e43a-8891-c82f-f23c91a70cca . _:0ae0983b-e43a-8891-c82f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Return Air Temperature" ; ph:dis "Bravo RTU-2 Return Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e43a-8892-c830-f23c91a70cca . _:0ae0983b-e43a-8892-c830-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Fan Status" ; ph:dis "Bravo RTU-2 Return Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e449-cac0-c831-f23c91a70cca . _:0ae0983b-e449-cac0-c831-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Return Fan VFD Speed" ; ph:dis "Bravo RTU-2 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e449-cac1-c832-f23c91a70cca . _:0ae0983b-e449-cac1-c832-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Flow" ; ph:dis "Bravo RTU-2 Supply Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e449-cac2-c833-f23c91a70cca . _:0ae0983b-e449-cac2-c833-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Humidity" ; ph:dis "Bravo RTU-2 Supply Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e449-cac3-c834-f23c91a70cca . _:0ae0983b-e449-cac3-c834-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00e9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e449-cac4-c835-f23c91a70cca . _:0ae0983b-e449-cac4-c835-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7045004074770955 ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e449-cac5-c836-f23c91a70cca . _:0ae0983b-e449-cac5-c836-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e449-cac6-c837-f23c91a70cca . _:0ae0983b-e449-cac6-c837-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature" ; ph:dis "Bravo RTU-2 Supply Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e449-cac7-c838-f23c91a70cca . _:0ae0983b-e449-cac7-c838-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e477-9180-c839-f23c91a70cca . _:0ae0983b-e477-9180-c839-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Fan Status" ; ph:dis "Bravo RTU-2 Supply Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e477-9181-c83a-f23c91a70cca . _:0ae0983b-e477-9181-c83a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-2 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e477-9182-c83b-f23c91a70cca . _:0ae0983b-e477-9182-c83b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00f0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-2 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e486-d3c0-c83c-f23c91a70cca . _:0ae0983b-e486-d3c0-c83c-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f1 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 VAV Total Flow" ; ph:dis "Bravo RTU-2 VAV Total Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e486-d3c1-c83d-f23c91a70cca . _:0ae0983b-e486-d3c1-c83d-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f2 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-3" ; ph:dis "Bravo RTU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0ae0983b-e486-d3c2-c83e-f23c91a70cca . _:0ae0983b-e486-d3c2-c83e-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 33600 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 318 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 6.7 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1346.1 ; _:designHotWaterFlow 53 ; _:designChilledWaterFlow 180.2 ; _:designReturnAirFlow 33600 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 33600 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 60 ; _:designReturnFanAirDeltaPressure 1.63 . _:b-00f3 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 AHU Operation Mode" ; ph:dis "Bravo RTU-3 AHU Operation Mode" ; phIoT:equipRef _:b-00f2 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e486-d3c3-c83f-f23c91a70cca . _:0ae0983b-e486-d3c3-c83f-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-3 Cooling Valve Output" ; ph:dis "Bravo RTU-3 Cooling Valve Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3c4-c840-f23c91a70cca . _:0ae0983b-e486-d3c4-c840-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-3 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3c5-c841-f23c91a70cca . _:0ae0983b-e486-d3c5-c841-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f6 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-3 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e486-d3c6-c842-f23c91a70cca . _:0ae0983b-e486-d3c6-c842-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00f7 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0ae0983b-e486-d3c7-c843-f23c91a70cca . _:0ae0983b-e486-d3c7-c843-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-3 Humidifier Enable" ; ph:dis "Bravo RTU-3 Humidifier Enable" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e486-d3c8-c844-f23c91a70cca . _:0ae0983b-e486-d3c8-c844-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00f9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-3 Humidifier Output" ; ph:dis "Bravo RTU-3 Humidifier Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3c9-c845-f23c91a70cca . _:0ae0983b-e486-d3c9-c845-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00fa a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-3 Max Damper Position" ; ph:dis "Bravo RTU-3 Max Damper Position" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3ca-c846-f23c91a70cca . _:0ae0983b-e486-d3ca-c846-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-3 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e486-d3cb-c847-f23c91a70cca . _:0ae0983b-e486-d3cb-c847-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3cc-c848-f23c91a70cca . _:0ae0983b-e486-d3cc-c848-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature" ; ph:dis "Bravo RTU-3 Mixed Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e486-d3cd-c849-f23c91a70cca . _:0ae0983b-e486-d3cd-c849-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e486-d3ce-c84a-f23c91a70cca . _:0ae0983b-e486-d3ce-c84a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-3 Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3cf-c84b-f23c91a70cca . _:0ae0983b-e486-d3cf-c84b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0100 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Outside Air Flow" ; ph:dis "Bravo RTU-3 Outside Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e486-d3d0-c84c-f23c91a70cca . _:0ae0983b-e486-d3d0-c84c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0101 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e486-d3d1-c84d-f23c91a70cca . _:0ae0983b-e486-d3d1-c84d-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0102 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Percent Outside Air" ; ph:dis "Bravo RTU-3 Percent Outside Air" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e486-d3d2-c84e-f23c91a70cca . _:0ae0983b-e486-d3d2-c84e-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0103 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return ; rdfs:label "Bravo RTU-3 Return Air Damper Output" ; ph:dis "Bravo RTU-3 Return Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e496-1600-c84f-f23c91a70cca . _:0ae0983b-e496-1600-c84f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0104 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Flow" ; ph:dis "Bravo RTU-3 Return Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e496-1601-c850-f23c91a70cca . _:0ae0983b-e496-1601-c850-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0105 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Humidity" ; ph:dis "Bravo RTU-3 Return Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e496-1602-c851-f23c91a70cca . _:0ae0983b-e496-1602-c851-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0106 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Return Air Temperature" ; ph:dis "Bravo RTU-3 Return Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e496-1603-c852-f23c91a70cca . _:0ae0983b-e496-1603-c852-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0107 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Fan Status" ; ph:dis "Bravo RTU-3 Return Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e496-1604-c853-f23c91a70cca . _:0ae0983b-e496-1604-c853-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0108 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Return Fan VFD Speed" ; ph:dis "Bravo RTU-3 Return Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e496-1605-c854-f23c91a70cca . _:0ae0983b-e496-1605-c854-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3324288739189246 ; _:sourcePointName "RTDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0109 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Flow" ; ph:dis "Bravo RTU-3 Supply Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e496-1606-c855-f23c91a70cca . _:0ae0983b-e496-1606-c855-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-010a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Humidity" ; ph:dis "Bravo RTU-3 Supply Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e496-1607-c856-f23c91a70cca . _:0ae0983b-e496-1607-c856-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-010b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-3 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e496-1608-c857-f23c91a70cca . _:0ae0983b-e496-1608-c857-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-010c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Static Pressure" ; ph:dis "Bravo RTU-3 Supply Air Static Pressure" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e496-1609-c858-f23c91a70cca . _:0ae0983b-e496-1609-c858-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-010d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature" ; ph:dis "Bravo RTU-3 Supply Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e496-160a-c859-f23c91a70cca . _:0ae0983b-e496-160a-c859-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-010e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e496-160b-c85a-f23c91a70cca . _:0ae0983b-e496-160b-c85a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-010f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Fan Status" ; ph:dis "Bravo RTU-3 Supply Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e496-160c-c85b-f23c91a70cca . _:0ae0983b-e496-160c-c85b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0110 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-3 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e496-160d-c85c-f23c91a70cca . _:0ae0983b-e496-160d-c85c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.32036669663302475 ; _:sourcePointName "SPDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0111 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-3 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e496-160e-c85d-f23c91a70cca . _:0ae0983b-e496-160e-c85d-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0112 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 VAV Total Flow" ; ph:dis "Bravo RTU-3 VAV Total Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e496-160f-c85e-f23c91a70cca . _:0ae0983b-e496-160f-c85e-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0113 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-4" ; ph:dis "Bravo RTU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0ae0983b-e496-1610-c85f-f23c91a70cca . _:0ae0983b-e496-1610-c85f-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15700 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 243 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 4.76 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1028.7 ; _:designHotWaterFlow 41 ; _:designChilledWaterFlow 137.8 ; _:designReturnAirFlow 25700 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 25700 ; _:designReturnFanPower 20 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.64 . _:b-0114 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 AHU Operation Mode" ; ph:dis "Bravo RTU-4 AHU Operation Mode" ; phIoT:equipRef _:b-0113 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e496-1611-c860-f23c91a70cca . _:0ae0983b-e496-1611-c860-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0115 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-4 Cooling Valve Output" ; ph:dis "Bravo RTU-4 Cooling Valve Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5840-c861-f23c91a70cca . _:0ae0983b-e4a5-5840-c861-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0116 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-4 Exhaust Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5841-c862-f23c91a70cca . _:0ae0983b-e4a5-5841-c862-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0117 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-4 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4a5-5842-c863-f23c91a70cca . _:0ae0983b-e4a5-5842-c863-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0118 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0ae0983b-e4a5-5843-c864-f23c91a70cca . _:0ae0983b-e4a5-5843-c864-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0119 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-4 Humidifier Enable" ; ph:dis "Bravo RTU-4 Humidifier Enable" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4a5-5844-c865-f23c91a70cca . _:0ae0983b-e4a5-5844-c865-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-011a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-4 Humidifier Output" ; ph:dis "Bravo RTU-4 Humidifier Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5845-c866-f23c91a70cca . _:0ae0983b-e4a5-5845-c866-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-011b a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-4 Max Damper Position" ; ph:dis "Bravo RTU-4 Max Damper Position" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5846-c867-f23c91a70cca . _:0ae0983b-e4a5-5846-c867-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-011c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5847-c868-f23c91a70cca . _:0ae0983b-e4a5-5847-c868-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-011d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4a5-5848-c869-f23c91a70cca . _:0ae0983b-e4a5-5848-c869-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-011e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5849-c86a-f23c91a70cca . _:0ae0983b-e4a5-5849-c86a-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-011f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature" ; ph:dis "Bravo RTU-4 Mixed Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4a5-584a-c86b-f23c91a70cca . _:0ae0983b-e4a5-584a-c86b-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0120 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4a5-584b-c86c-f23c91a70cca . _:0ae0983b-e4a5-584b-c86c-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0121 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-4 Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-584c-c86d-f23c91a70cca . _:0ae0983b-e4a5-584c-c86d-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0122 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Outside Air Flow" ; ph:dis "Bravo RTU-4 Outside Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4a5-584d-c86e-f23c91a70cca . _:0ae0983b-e4a5-584d-c86e-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0123 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4a5-584e-c86f-f23c91a70cca . _:0ae0983b-e4a5-584e-c86f-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0124 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Percent Outside Air" ; ph:dis "Bravo RTU-4 Percent Outside Air" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-584f-c870-f23c91a70cca . _:0ae0983b-e4a5-584f-c870-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0125 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Damper Output" ; ph:dis "Bravo RTU-4 Return Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5850-c871-f23c91a70cca . _:0ae0983b-e4a5-5850-c871-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0126 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Flow" ; ph:dis "Bravo RTU-4 Return Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4a5-5851-c872-f23c91a70cca . _:0ae0983b-e4a5-5851-c872-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0127 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Humidity" ; ph:dis "Bravo RTU-4 Return Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4a5-5852-c873-f23c91a70cca . _:0ae0983b-e4a5-5852-c873-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0128 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Return Air Temperature" ; ph:dis "Bravo RTU-4 Return Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4b4-9a80-c874-f23c91a70cca . _:0ae0983b-e4b4-9a80-c874-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0129 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Fan Status" ; ph:dis "Bravo RTU-4 Return Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4b4-9a81-c875-f23c91a70cca . _:0ae0983b-e4b4-9a81-c875-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-4 Return Fan VFD Speed" ; ph:dis "Bravo RTU-4 Return Fan VFD Speed" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4e2-6140-c876-f23c91a70cca . _:0ae0983b-e4e2-6140-c876-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-012b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Flow" ; ph:dis "Bravo RTU-4 Supply Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4e2-6141-c877-f23c91a70cca . _:0ae0983b-e4e2-6141-c877-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Humidity" ; ph:dis "Bravo RTU-4 Supply Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4e2-6142-c878-f23c91a70cca . _:0ae0983b-e4e2-6142-c878-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4e2-6143-c879-f23c91a70cca . _:0ae0983b-e4e2-6143-c879-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-012e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e4e2-6144-c87a-f23c91a70cca . _:0ae0983b-e4e2-6144-c87a-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Static Pressure" ; ph:dis "Bravo RTU-4 Supply Air Static Pressure" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0ae0983b-e4e2-6145-c87b-f23c91a70cca . _:0ae0983b-e4e2-6145-c87b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0130 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature" ; ph:dis "Bravo RTU-4 Supply Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4e2-6146-c87c-f23c91a70cca . _:0ae0983b-e4e2-6146-c87c-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0131 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4e2-6147-c87d-f23c91a70cca . _:0ae0983b-e4e2-6147-c87d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0132 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Fan Status" ; ph:dis "Bravo RTU-4 Supply Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4e2-6148-c87e-f23c91a70cca . _:0ae0983b-e4e2-6148-c87e-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0133 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-4 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a380-c87f-f23c91a70cca . _:0ae0983b-e4f1-a380-c87f-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0134 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 VAV Total Flow" ; ph:dis "Bravo RTU-4 VAV Total Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a381-c880-f23c91a70cca . _:0ae0983b-e4f1-a381-c880-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0135 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo RTUs" ; ph:dis "Bravo RTUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e4f1-a382-c881-f23c91a70cca . _:0ae0983b-e4f1-a382-c881-f23c91a70cca rdfs:label "" . _:b-0136 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler A" ; ph:dis "Bravo Steam Boiler A" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0ae0983b-e4f1-a383-c882-f23c91a70cca . _:0ae0983b-e4f1-a383-c882-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0137 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler A Boiler Status" ; ph:dis "Bravo Steam Boiler A Boiler Status" ; phIoT:equipRef _:b-0136 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4f1-a384-c883-f23c91a70cca . _:0ae0983b-e4f1-a384-c883-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrAsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0138 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler B" ; ph:dis "Bravo Steam Boiler B" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0ae0983b-e4f1-a385-c884-f23c91a70cca . _:0ae0983b-e4f1-a385-c884-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0139 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler B Boiler Status" ; ph:dis "Bravo Steam Boiler B Boiler Status" ; phIoT:equipRef _:b-0138 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4f1-a386-c885-f23c91a70cca . _:0ae0983b-e4f1-a386-c885-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrBsts" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-013a a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler C" ; ph:dis "Bravo Steam Boiler C" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0ae0983b-e4f1-a387-c886-f23c91a70cca . _:0ae0983b-e4f1-a387-c886-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-013b a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler C Boiler Status" ; ph:dis "Bravo Steam Boiler C Boiler Status" ; phIoT:equipRef _:b-013a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0ae0983b-e4f1-a388-c887-f23c91a70cca . _:0ae0983b-e4f1-a388-c887-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrCsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-013c a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Steam System" ; ph:dis "Bravo Steam System" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-e4f1-a389-c888-f23c91a70cca . _:0ae0983b-e4f1-a389-c888-f23c91a70cca rdfs:label "" . _:b-013d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-1" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e4f1-a38a-c889-f23c91a70cca . _:0ae0983b-e4f1-a38a-c889-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-013e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-1 Damper Output" ; ph:dis "Bravo VAV 1-1 Damper Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4f1-a38b-c88a-f23c91a70cca . _:0ae0983b-e4f1-a38b-c88a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-013f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a38c-c88b-f23c91a70cca . _:0ae0983b-e4f1-a38c-c88b-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0140 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a38d-c88c-f23c91a70cca . _:0ae0983b-e4f1-a38d-c88c-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0141 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-1 Heating Valve Output" ; ph:dis "Bravo VAV 1-1 Heating Valve Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4f1-a38e-c88d-f23c91a70cca . _:0ae0983b-e4f1-a38e-c88d-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0142 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4f1-a38f-c88e-f23c91a70cca . _:0ae0983b-e4f1-a38f-c88e-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0143 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Temperature" ; ph:dis "Bravo VAV 1-1 Zone Temperature" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e4f1-a390-c88f-f23c91a70cca . _:0ae0983b-e4f1-a390-c88f-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0144 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-10" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e4f1-a391-c890-f23c91a70cca . _:0ae0983b-e4f1-a391-c890-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-0145 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-10 Damper Output" ; ph:dis "Bravo VAV 1-10 Damper Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e4f1-a392-c891-f23c91a70cca . _:0ae0983b-e4f1-a392-c891-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0146 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a393-c892-f23c91a70cca . _:0ae0983b-e4f1-a393-c892-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0147 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e4f1-a394-c893-f23c91a70cca . _:0ae0983b-e4f1-a394-c893-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0148 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-10 Heating Valve Output" ; ph:dis "Bravo VAV 1-10 Heating Valve Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e500-e5c0-c894-f23c91a70cca . _:0ae0983b-e500-e5c0-c894-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0149 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-10 Supply Air Temperature" ; ph:dis "Bravo VAV 1-10 Supply Air Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5c1-c895-f23c91a70cca . _:0ae0983b-e500-e5c1-c895-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5c2-c896-f23c91a70cca . _:0ae0983b-e500-e5c2-c896-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-014b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Temperature" ; ph:dis "Bravo VAV 1-10 Zone Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5c3-c897-f23c91a70cca . _:0ae0983b-e500-e5c3-c897-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-014c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-11" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e500-e5c4-c898-f23c91a70cca . _:0ae0983b-e500-e5c4-c898-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-014d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-11 Damper Output" ; ph:dis "Bravo VAV 1-11 Damper Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e500-e5c5-c899-f23c91a70cca . _:0ae0983b-e500-e5c5-c899-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-014e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e500-e5c6-c89a-f23c91a70cca . _:0ae0983b-e500-e5c6-c89a-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e500-e5c7-c89b-f23c91a70cca . _:0ae0983b-e500-e5c7-c89b-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0150 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-11 Heating Valve Output" ; ph:dis "Bravo VAV 1-11 Heating Valve Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e500-e5c8-c89c-f23c91a70cca . _:0ae0983b-e500-e5c8-c89c-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0151 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-11 Supply Air Temperature" ; ph:dis "Bravo VAV 1-11 Supply Air Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5c9-c89d-f23c91a70cca . _:0ae0983b-e500-e5c9-c89d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0152 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5ca-c89e-f23c91a70cca . _:0ae0983b-e500-e5ca-c89e-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0153 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Temperature" ; ph:dis "Bravo VAV 1-11 Zone Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5cb-c89f-f23c91a70cca . _:0ae0983b-e500-e5cb-c89f-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0154 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-12" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e500-e5cc-c8a0-f23c91a70cca . _:0ae0983b-e500-e5cc-c8a0-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0155 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-12 Damper Output" ; ph:dis "Bravo VAV 1-12 Damper Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e500-e5cd-c8a1-f23c91a70cca . _:0ae0983b-e500-e5cd-c8a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0156 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e500-e5ce-c8a2-f23c91a70cca . _:0ae0983b-e500-e5ce-c8a2-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0157 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e500-e5cf-c8a3-f23c91a70cca . _:0ae0983b-e500-e5cf-c8a3-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0158 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-12 Heating Valve Output" ; ph:dis "Bravo VAV 1-12 Heating Valve Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e500-e5d0-c8a4-f23c91a70cca . _:0ae0983b-e500-e5d0-c8a4-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0159 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-12 Supply Air Temperature" ; ph:dis "Bravo VAV 1-12 Supply Air Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e500-e5d1-c8a5-f23c91a70cca . _:0ae0983b-e500-e5d1-c8a5-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-015a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e510-2800-c8a6-f23c91a70cca . _:0ae0983b-e510-2800-c8a6-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Temperature" ; ph:dis "Bravo VAV 1-12 Zone Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e510-2801-c8a7-f23c91a70cca . _:0ae0983b-e510-2801-c8a7-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-015c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-13" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e510-2802-c8a8-f23c91a70cca . _:0ae0983b-e510-2802-c8a8-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 27 ; _:designHotWaterFlow 3 ; _:designAirFlow 1000 . _:b-015d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-13 Damper Output" ; ph:dis "Bravo VAV 1-13 Damper Output" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e510-2803-c8a9-f23c91a70cca . _:0ae0983b-e510-2803-c8a9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-015e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e510-2804-c8aa-f23c91a70cca . _:0ae0983b-e510-2804-c8aa-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e510-2805-c8ab-f23c91a70cca . _:0ae0983b-e510-2805-c8ab-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0160 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-13 Heating Valve" ; ph:dis "Bravo VAV 1-13 Heating Valve" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e510-2806-c8ac-f23c91a70cca . _:0ae0983b-e510-2806-c8ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0161 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-13 Supply Air Temperature" ; ph:dis "Bravo VAV 1-13 Supply Air Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e510-2807-c8ad-f23c91a70cca . _:0ae0983b-e510-2807-c8ad-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0162 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e510-2808-c8ae-f23c91a70cca . _:0ae0983b-e510-2808-c8ae-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0163 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Temperature" ; ph:dis "Bravo VAV 1-13 Zone Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e510-2809-c8af-f23c91a70cca . _:0ae0983b-e510-2809-c8af-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0164 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-14" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e510-280a-c8b0-f23c91a70cca . _:0ae0983b-e510-280a-c8b0-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-0165 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-14 Damper Output" ; ph:dis "Bravo VAV 1-14 Damper Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e510-280b-c8b1-f23c91a70cca . _:0ae0983b-e510-280b-c8b1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0166 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e510-280c-c8b2-f23c91a70cca . _:0ae0983b-e510-280c-c8b2-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0167 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e510-280d-c8b3-f23c91a70cca . _:0ae0983b-e510-280d-c8b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0168 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-14 Heating Valve Output" ; ph:dis "Bravo VAV 1-14 Heating Valve Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e54d-3100-c8b4-f23c91a70cca . _:0ae0983b-e54d-3100-c8b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0169 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-14 Supply Air Temperature" ; ph:dis "Bravo VAV 1-14 Supply Air Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-3101-c8b5-f23c91a70cca . _:0ae0983b-e54d-3101-c8b5-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-016a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-3102-c8b6-f23c91a70cca . _:0ae0983b-e54d-3102-c8b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-016b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Temperature" ; ph:dis "Bravo VAV 1-14 Zone Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-3103-c8b7-f23c91a70cca . _:0ae0983b-e54d-3103-c8b7-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-016c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-15" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e54d-3104-c8b8-f23c91a70cca . _:0ae0983b-e54d-3104-c8b8-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-016d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-15 Damper Output" ; ph:dis "Bravo VAV 1-15 Damper Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e54d-3105-c8b9-f23c91a70cca . _:0ae0983b-e54d-3105-c8b9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-016e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e54d-3106-c8ba-f23c91a70cca . _:0ae0983b-e54d-3106-c8ba-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-016f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e54d-3107-c8bb-f23c91a70cca . _:0ae0983b-e54d-3107-c8bb-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0170 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-15 Heating Valve Output" ; ph:dis "Bravo VAV 1-15 Heating Valve Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e54d-3108-c8bc-f23c91a70cca . _:0ae0983b-e54d-3108-c8bc-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0171 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-15 Supply Air Temperature" ; ph:dis "Bravo VAV 1-15 Supply Air Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-3109-c8bd-f23c91a70cca . _:0ae0983b-e54d-3109-c8bd-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0172 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-310a-c8be-f23c91a70cca . _:0ae0983b-e54d-310a-c8be-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0173 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Temperature" ; ph:dis "Bravo VAV 1-15 Zone Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e54d-310b-c8bf-f23c91a70cca . _:0ae0983b-e54d-310b-c8bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0174 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-16" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e54d-310c-c8c0-f23c91a70cca . _:0ae0983b-e54d-310c-c8c0-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0175 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-16 Damper Output" ; ph:dis "Bravo VAV 1-16 Damper Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e54d-310d-c8c1-f23c91a70cca . _:0ae0983b-e54d-310d-c8c1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0176 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7340-c8c2-f23c91a70cca . _:0ae0983b-e55c-7340-c8c2-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0177 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7341-c8c3-f23c91a70cca . _:0ae0983b-e55c-7341-c8c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0178 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-16 Heating Valve Output" ; ph:dis "Bravo VAV 1-16 Heating Valve Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e55c-7342-c8c4-f23c91a70cca . _:0ae0983b-e55c-7342-c8c4-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0179 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-16 Supply Air Temperature" ; ph:dis "Bravo VAV 1-16 Supply Air Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-7343-c8c5-f23c91a70cca . _:0ae0983b-e55c-7343-c8c5-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-7344-c8c6-f23c91a70cca . _:0ae0983b-e55c-7344-c8c6-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-017b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Temperature" ; ph:dis "Bravo VAV 1-16 Zone Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-7345-c8c7-f23c91a70cca . _:0ae0983b-e55c-7345-c8c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-017c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-17" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e55c-7346-c8c8-f23c91a70cca . _:0ae0983b-e55c-7346-c8c8-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-017d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-17 Damper Output" ; ph:dis "Bravo VAV 1-17 Damper Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e55c-7347-c8c9-f23c91a70cca . _:0ae0983b-e55c-7347-c8c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7348-c8ca-f23c91a70cca . _:0ae0983b-e55c-7348-c8ca-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7349-c8cb-f23c91a70cca . _:0ae0983b-e55c-7349-c8cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0180 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-17 Heating Valve Output" ; ph:dis "Bravo VAV 1-17 Heating Valve Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e55c-734a-c8cc-f23c91a70cca . _:0ae0983b-e55c-734a-c8cc-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0181 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-17 Supply Air Temperature" ; ph:dis "Bravo VAV 1-17 Supply Air Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-734b-c8cd-f23c91a70cca . _:0ae0983b-e55c-734b-c8cd-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0182 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-734c-c8ce-f23c91a70cca . _:0ae0983b-e55c-734c-c8ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0183 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Temperature" ; ph:dis "Bravo VAV 1-17 Zone Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e55c-734d-c8cf-f23c91a70cca . _:0ae0983b-e55c-734d-c8cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0184 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-18" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e55c-734e-c8d0-f23c91a70cca . _:0ae0983b-e55c-734e-c8d0-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0185 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-18 Damper Output" ; ph:dis "Bravo VAV 1-18 Damper Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e55c-734f-c8d1-f23c91a70cca . _:0ae0983b-e55c-734f-c8d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0186 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7350-c8d2-f23c91a70cca . _:0ae0983b-e55c-7350-c8d2-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0187 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e55c-7351-c8d3-f23c91a70cca . _:0ae0983b-e55c-7351-c8d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0188 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-18 Heating Valve Output" ; ph:dis "Bravo VAV 1-18 Heating Valve Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e55c-7352-c8d4-f23c91a70cca . _:0ae0983b-e55c-7352-c8d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0189 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-18 Supply Air Temperature" ; ph:dis "Bravo VAV 1-18 Supply Air Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b580-c8d5-f23c91a70cca . _:0ae0983b-e56b-b580-c8d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-018a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b581-c8d6-f23c91a70cca . _:0ae0983b-e56b-b581-c8d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-018b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Temperature" ; ph:dis "Bravo VAV 1-18 Zone Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b582-c8d7-f23c91a70cca . _:0ae0983b-e56b-b582-c8d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-018c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-19" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e56b-b583-c8d8-f23c91a70cca . _:0ae0983b-e56b-b583-c8d8-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 30.9 ; _:designHotWaterFlow 1.45 ; _:designAirFlow 2400 . _:b-018d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-19 Damper Output" ; ph:dis "Bravo VAV 1-19 Damper Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e56b-b584-c8d9-f23c91a70cca . _:0ae0983b-e56b-b584-c8d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e56b-b585-c8da-f23c91a70cca . _:0ae0983b-e56b-b585-c8da-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e56b-b586-c8db-f23c91a70cca . _:0ae0983b-e56b-b586-c8db-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0190 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-19 Heating Valve Output" ; ph:dis "Bravo VAV 1-19 Heating Valve Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e56b-b587-c8dc-f23c91a70cca . _:0ae0983b-e56b-b587-c8dc-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0191 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-19 Supply Air Temperature" ; ph:dis "Bravo VAV 1-19 Supply Air Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b588-c8dd-f23c91a70cca . _:0ae0983b-e56b-b588-c8dd-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0192 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Humidity" ; ph:dis "Bravo VAV 1-19 Zone Air Humidity" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e56b-b589-c8de-f23c91a70cca . _:0ae0983b-e56b-b589-c8de-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6984488664169048 ; _:sourcePointName "Humidity" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0193 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b58a-c8df-f23c91a70cca . _:0ae0983b-e56b-b58a-c8df-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0194 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Temperature" ; ph:dis "Bravo VAV 1-19 Zone Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e56b-b58b-c8e0-f23c91a70cca . _:0ae0983b-e56b-b58b-c8e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0195 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-2" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e56b-b58c-c8e1-f23c91a70cca . _:0ae0983b-e56b-b58c-c8e1-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.5 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-0196 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-2 Damper Output" ; ph:dis "Bravo VAV 1-2 Damper Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e56b-b58d-c8e2-f23c91a70cca . _:0ae0983b-e56b-b58d-c8e2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0197 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e56b-b58e-c8e3-f23c91a70cca . _:0ae0983b-e56b-b58e-c8e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0198 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e57a-f7c0-c8e4-f23c91a70cca . _:0ae0983b-e57a-f7c0-c8e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0199 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-2 Heating Valve Output" ; ph:dis "Bravo VAV 1-2 Heating Valve Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e57a-f7c1-c8e5-f23c91a70cca . _:0ae0983b-e57a-f7c1-c8e5-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-2 Supply Air Temperature" ; ph:dis "Bravo VAV 1-2 Supply Air Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e57a-f7c2-c8e6-f23c91a70cca . _:0ae0983b-e57a-f7c2-c8e6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-019b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e57a-f7c3-c8e7-f23c91a70cca . _:0ae0983b-e57a-f7c3-c8e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-019c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Temperature" ; ph:dis "Bravo VAV 1-2 Zone Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e57a-f7c4-c8e8-f23c91a70cca . _:0ae0983b-e57a-f7c4-c8e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-20" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e57a-f7c5-c8e9-f23c91a70cca . _:0ae0983b-e57a-f7c5-c8e9-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 0.28 ; _:designAirFlow 800 . _:b-019e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-20 Damper Output" ; ph:dis "Bravo VAV 1-20 Damper Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5a8-be80-c8ea-f23c91a70cca . _:0ae0983b-e5a8-be80-c8ea-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-019f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5a8-be81-c8eb-f23c91a70cca . _:0ae0983b-e5a8-be81-c8eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5b8-00c0-c8ec-f23c91a70cca . _:0ae0983b-e5b8-00c0-c8ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-20 Heating Valve Output" ; ph:dis "Bravo VAV 1-20 Heating Valve Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00c1-c8ed-f23c91a70cca . _:0ae0983b-e5b8-00c1-c8ed-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-20 Supply Air Temperature" ; ph:dis "Bravo VAV 1-20 Supply Air Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00c2-c8ee-f23c91a70cca . _:0ae0983b-e5b8-00c2-c8ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00c3-c8ef-f23c91a70cca . _:0ae0983b-e5b8-00c3-c8ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Temperature" ; ph:dis "Bravo VAV 1-20 Zone Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00c4-c8f0-f23c91a70cca . _:0ae0983b-e5b8-00c4-c8f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a5 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-3" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5b8-00c5-c8f1-f23c91a70cca . _:0ae0983b-e5b8-00c5-c8f1-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-3 Damper Output" ; ph:dis "Bravo VAV 1-3 Damper Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00c6-c8f2-f23c91a70cca . _:0ae0983b-e5b8-00c6-c8f2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5b8-00c7-c8f3-f23c91a70cca . _:0ae0983b-e5b8-00c7-c8f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5b8-00c8-c8f4-f23c91a70cca . _:0ae0983b-e5b8-00c8-c8f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-3 Heating Valve Output" ; ph:dis "Bravo VAV 1-3 Heating Valve Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00c9-c8f5-f23c91a70cca . _:0ae0983b-e5b8-00c9-c8f5-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Supply Air Humidity" ; ph:dis "Bravo VAV 1-3 Supply Air Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00ca-c8f6-f23c91a70cca . _:0ae0983b-e5b8-00ca-c8f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-3 Supply Air Temperature" ; ph:dis "Bravo VAV 1-3 Supply Air Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00cb-c8f7-f23c91a70cca . _:0ae0983b-e5b8-00cb-c8f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00cc-c8f8-f23c91a70cca . _:0ae0983b-e5b8-00cc-c8f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-3 Zone Relative Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00cd-c8f9-f23c91a70cca . _:0ae0983b-e5b8-00cd-c8f9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7237593125289187 ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Temperature" ; ph:dis "Bravo VAV 1-3 Zone Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5b8-00ce-c8fa-f23c91a70cca . _:0ae0983b-e5b8-00ce-c8fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01af a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-4" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5b8-00cf-c8fb-f23c91a70cca . _:0ae0983b-e5b8-00cf-c8fb-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 3.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-4 Damper Output" ; ph:dis "Bravo VAV 1-4 Damper Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5b8-00d0-c8fc-f23c91a70cca . _:0ae0983b-e5b8-00d0-c8fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01b1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5b8-00d1-c8fd-f23c91a70cca . _:0ae0983b-e5b8-00d1-c8fd-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5b8-00d2-c8fe-f23c91a70cca . _:0ae0983b-e5b8-00d2-c8fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-4 Heating Valve Output" ; ph:dis "Bravo VAV 1-4 Heating Valve Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-4300-c8ff-f23c91a70cca . _:0ae0983b-e5c7-4300-c8ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-4 Supply Air Temperature" ; ph:dis "Bravo VAV 1-4 Supply Air Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-4301-c900-f23c91a70cca . _:0ae0983b-e5c7-4301-c900-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-4302-c901-f23c91a70cca . _:0ae0983b-e5c7-4302-c901-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Temperature" ; ph:dis "Bravo VAV 1-4 Zone Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-4303-c902-f23c91a70cca . _:0ae0983b-e5c7-4303-c902-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01b7 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-5" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5c7-4304-c903-f23c91a70cca . _:0ae0983b-e5c7-4304-c903-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 450 . _:b-01b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-5 Damper Output" ; ph:dis "Bravo VAV 1-5 Damper Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-4305-c904-f23c91a70cca . _:0ae0983b-e5c7-4305-c904-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5c7-4306-c905-f23c91a70cca . _:0ae0983b-e5c7-4306-c905-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5c7-4307-c906-f23c91a70cca . _:0ae0983b-e5c7-4307-c906-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-5 Heating Valve Output" ; ph:dis "Bravo VAV 1-5 Heating Valve Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-4308-c907-f23c91a70cca . _:0ae0983b-e5c7-4308-c907-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-5 Supply Air Temperature" ; ph:dis "Bravo VAV 1-5 Supply Air Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-4309-c908-f23c91a70cca . _:0ae0983b-e5c7-4309-c908-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-430a-c909-f23c91a70cca . _:0ae0983b-e5c7-430a-c909-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Temperature" ; ph:dis "Bravo VAV 1-5 Zone Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5c7-430b-c90a-f23c91a70cca . _:0ae0983b-e5c7-430b-c90a-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01bf a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-6" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5c7-430c-c90b-f23c91a70cca . _:0ae0983b-e5c7-430c-c90b-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-6 Damper Output" ; ph:dis "Bravo VAV 1-6 Damper Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-430d-c90c-f23c91a70cca . _:0ae0983b-e5c7-430d-c90c-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5c7-430e-c90d-f23c91a70cca . _:0ae0983b-e5c7-430e-c90d-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5c7-430f-c90e-f23c91a70cca . _:0ae0983b-e5c7-430f-c90e-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-6 Heating Valve Output" ; ph:dis "Bravo VAV 1-6 Heating Valve Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-4310-c90f-f23c91a70cca . _:0ae0983b-e5c7-4310-c90f-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Supply Air Humidity" ; ph:dis "Bravo VAV 1-6 Supply Air Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5c7-4311-c910-f23c91a70cca . _:0ae0983b-e5c7-4311-c910-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-6 Supply Air Temperature" ; ph:dis "Bravo VAV 1-6 Supply Air Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-8540-c911-f23c91a70cca . _:0ae0983b-e5d6-8540-c911-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-8541-c912-f23c91a70cca . _:0ae0983b-e5d6-8541-c912-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-6 Zone Relative Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5d6-8542-c913-f23c91a70cca . _:0ae0983b-e5d6-8542-c913-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Temperature" ; ph:dis "Bravo VAV 1-6 Zone Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-8543-c914-f23c91a70cca . _:0ae0983b-e5d6-8543-c914-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-7" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5d6-8544-c915-f23c91a70cca . _:0ae0983b-e5d6-8544-c915-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 450 . _:b-01ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-7 Damper Output" ; ph:dis "Bravo VAV 1-7 Damper Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5d6-8545-c916-f23c91a70cca . _:0ae0983b-e5d6-8545-c916-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5d6-8546-c917-f23c91a70cca . _:0ae0983b-e5d6-8546-c917-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5d6-8547-c918-f23c91a70cca . _:0ae0983b-e5d6-8547-c918-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-7 Heating Valve Output" ; ph:dis "Bravo VAV 1-7 Heating Valve Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5d6-8548-c919-f23c91a70cca . _:0ae0983b-e5d6-8548-c919-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-7 Supply Air Temperature" ; ph:dis "Bravo VAV 1-7 Supply Air Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-8549-c91a-f23c91a70cca . _:0ae0983b-e5d6-8549-c91a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-854a-c91b-f23c91a70cca . _:0ae0983b-e5d6-854a-c91b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Temperature" ; ph:dis "Bravo VAV 1-7 Zone Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-854b-c91c-f23c91a70cca . _:0ae0983b-e5d6-854b-c91c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-8" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e5d6-854c-c91d-f23c91a70cca . _:0ae0983b-e5d6-854c-c91d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-8 Damper Output" ; ph:dis "Bravo VAV 1-8 Damper Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5d6-854d-c91e-f23c91a70cca . _:0ae0983b-e5d6-854d-c91e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5d6-854e-c91f-f23c91a70cca . _:0ae0983b-e5d6-854e-c91f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e5d6-854f-c920-f23c91a70cca . _:0ae0983b-e5d6-854f-c920-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-8 Heating Valve Output" ; ph:dis "Bravo VAV 1-8 Heating Valve Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e5d6-8550-c921-f23c91a70cca . _:0ae0983b-e5d6-8550-c921-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-8 Supply Air Temperature" ; ph:dis "Bravo VAV 1-8 Supply Air Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5d6-8551-c922-f23c91a70cca . _:0ae0983b-e5d6-8551-c922-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5e5-c780-c923-f23c91a70cca . _:0ae0983b-e5e5-c780-c923-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Temperature" ; ph:dis "Bravo VAV 1-8 Zone Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e5e5-c781-c924-f23c91a70cca . _:0ae0983b-e5e5-c781-c924-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-9" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e613-8e40-c925-f23c91a70cca . _:0ae0983b-e613-8e40-c925-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 15.3 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 875 . _:b-01da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-9 Damper Output" ; ph:dis "Bravo VAV 1-9 Damper Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e613-8e41-c926-f23c91a70cca . _:0ae0983b-e613-8e41-c926-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e613-8e42-c927-f23c91a70cca . _:0ae0983b-e613-8e42-c927-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e613-8e43-c928-f23c91a70cca . _:0ae0983b-e613-8e43-c928-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-9 Heating Valve Output" ; ph:dis "Bravo VAV 1-9 Heating Valve Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e613-8e44-c929-f23c91a70cca . _:0ae0983b-e613-8e44-c929-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-9 Supply Air Temperature" ; ph:dis "Bravo VAV 1-9 Supply Air Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e613-8e45-c92a-f23c91a70cca . _:0ae0983b-e613-8e45-c92a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e613-8e46-c92b-f23c91a70cca . _:0ae0983b-e613-8e46-c92b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Temperature" ; ph:dis "Bravo VAV 1-9 Zone Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e613-8e47-c92c-f23c91a70cca . _:0ae0983b-e613-8e47-c92c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-1" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e613-8e48-c92d-f23c91a70cca . _:0ae0983b-e613-8e48-c92d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-1 Damper Output" ; ph:dis "Bravo VAV 2-1 Damper Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e622-d080-c92e-f23c91a70cca . _:0ae0983b-e622-d080-c92e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e622-d081-c92f-f23c91a70cca . _:0ae0983b-e622-d081-c92f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e622-d082-c930-f23c91a70cca . _:0ae0983b-e622-d082-c930-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-1 Heating Valve Output" ; ph:dis "Bravo VAV 2-1 Heating Valve Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e622-d083-c931-f23c91a70cca . _:0ae0983b-e622-d083-c931-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-1 Supply Air Temperature" ; ph:dis "Bravo VAV 2-1 Supply Air Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d084-c932-f23c91a70cca . _:0ae0983b-e622-d084-c932-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d085-c933-f23c91a70cca . _:0ae0983b-e622-d085-c933-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Temperature" ; ph:dis "Bravo VAV 2-1 Zone Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d086-c934-f23c91a70cca . _:0ae0983b-e622-d086-c934-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-10" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e622-d087-c935-f23c91a70cca . _:0ae0983b-e622-d087-c935-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 4.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 175 . _:b-01ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-10 Damper Output" ; ph:dis "Bravo VAV 2-10 Damper Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e622-d088-c936-f23c91a70cca . _:0ae0983b-e622-d088-c936-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e622-d089-c937-f23c91a70cca . _:0ae0983b-e622-d089-c937-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e622-d08a-c938-f23c91a70cca . _:0ae0983b-e622-d08a-c938-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-10 Heating Valve Output" ; ph:dis "Bravo VAV 2-10 Heating Valve Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e622-d08b-c939-f23c91a70cca . _:0ae0983b-e622-d08b-c939-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-10 Supply Air Temperature" ; ph:dis "Bravo VAV 2-10 Supply Air Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d08c-c93a-f23c91a70cca . _:0ae0983b-e622-d08c-c93a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d08d-c93b-f23c91a70cca . _:0ae0983b-e622-d08d-c93b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Temperature" ; ph:dis "Bravo VAV 2-10 Zone Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e622-d08e-c93c-f23c91a70cca . _:0ae0983b-e622-d08e-c93c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-11" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e622-d08f-c93d-f23c91a70cca . _:0ae0983b-e622-d08f-c93d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-11 Damper Output" ; ph:dis "Bravo VAV 2-11 Damper Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e622-d090-c93e-f23c91a70cca . _:0ae0983b-e622-d090-c93e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e622-d091-c93f-f23c91a70cca . _:0ae0983b-e622-d091-c93f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e632-12c0-c940-f23c91a70cca . _:0ae0983b-e632-12c0-c940-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-11 Heating Valve Output" ; ph:dis "Bravo VAV 2-11 Heating Valve Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e632-12c1-c941-f23c91a70cca . _:0ae0983b-e632-12c1-c941-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-11 Supply Air Temperature" ; ph:dis "Bravo VAV 2-11 Supply Air Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12c2-c942-f23c91a70cca . _:0ae0983b-e632-12c2-c942-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12c3-c943-f23c91a70cca . _:0ae0983b-e632-12c3-c943-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Temperature" ; ph:dis "Bravo VAV 2-11 Zone Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12c4-c944-f23c91a70cca . _:0ae0983b-e632-12c4-c944-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-12" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e632-12c5-c945-f23c91a70cca . _:0ae0983b-e632-12c5-c945-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-01fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-12 Damper Output" ; ph:dis "Bravo VAV 2-12 Damper Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e632-12c6-c946-f23c91a70cca . _:0ae0983b-e632-12c6-c946-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e632-12c7-c947-f23c91a70cca . _:0ae0983b-e632-12c7-c947-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e632-12c8-c948-f23c91a70cca . _:0ae0983b-e632-12c8-c948-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-12 Heating Valve Output" ; ph:dis "Bravo VAV 2-12 Heating Valve Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e632-12c9-c949-f23c91a70cca . _:0ae0983b-e632-12c9-c949-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-12 Supply Air Temperature" ; ph:dis "Bravo VAV 2-12 Supply Air Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12ca-c94a-f23c91a70cca . _:0ae0983b-e632-12ca-c94a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12cb-c94b-f23c91a70cca . _:0ae0983b-e632-12cb-c94b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0200 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Temperature" ; ph:dis "Bravo VAV 2-12 Zone Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12cc-c94c-f23c91a70cca . _:0ae0983b-e632-12cc-c94c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0201 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-13" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e632-12cd-c94d-f23c91a70cca . _:0ae0983b-e632-12cd-c94d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0202 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-13 Damper Output" ; ph:dis "Bravo VAV 2-13 Damper Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e632-12ce-c94e-f23c91a70cca . _:0ae0983b-e632-12ce-c94e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0203 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e632-12cf-c94f-f23c91a70cca . _:0ae0983b-e632-12cf-c94f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0204 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e632-12d0-c950-f23c91a70cca . _:0ae0983b-e632-12d0-c950-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0205 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-13 Heating Valve Output" ; ph:dis "Bravo VAV 2-13 Heating Valve Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e632-12d1-c951-f23c91a70cca . _:0ae0983b-e632-12d1-c951-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0206 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-13 Supply Air Temperature" ; ph:dis "Bravo VAV 2-13 Supply Air Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e632-12d2-c952-f23c91a70cca . _:0ae0983b-e632-12d2-c952-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0207 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e641-5500-c953-f23c91a70cca . _:0ae0983b-e641-5500-c953-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0208 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Temperature" ; ph:dis "Bravo VAV 2-13 Zone Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e641-5501-c954-f23c91a70cca . _:0ae0983b-e641-5501-c954-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0209 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-14" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e641-5502-c955-f23c91a70cca . _:0ae0983b-e641-5502-c955-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 24.2 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1450 . _:b-020a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-14 Damper Output" ; ph:dis "Bravo VAV 2-14 Damper Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e641-5503-c956-f23c91a70cca . _:0ae0983b-e641-5503-c956-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-020b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e641-5504-c957-f23c91a70cca . _:0ae0983b-e641-5504-c957-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-020c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e641-5505-c958-f23c91a70cca . _:0ae0983b-e641-5505-c958-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-020d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-14 Heating Valve Output" ; ph:dis "Bravo VAV 2-14 Heating Valve Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e641-5506-c959-f23c91a70cca . _:0ae0983b-e641-5506-c959-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-020e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-14 Supply Air Temperature" ; ph:dis "Bravo VAV 2-14 Supply Air Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e641-5507-c95a-f23c91a70cca . _:0ae0983b-e641-5507-c95a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-020f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e641-5508-c95b-f23c91a70cca . _:0ae0983b-e641-5508-c95b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0210 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Temperature" ; ph:dis "Bravo VAV 2-14 Zone Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e641-5509-c95c-f23c91a70cca . _:0ae0983b-e641-5509-c95c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0211 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-15" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e641-550a-c95d-f23c91a70cca . _:0ae0983b-e641-550a-c95d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0212 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-15 Damper Output" ; ph:dis "Bravo VAV 2-15 Damper Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e67e-5e00-c95e-f23c91a70cca . _:0ae0983b-e67e-5e00-c95e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0213 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e67e-5e01-c95f-f23c91a70cca . _:0ae0983b-e67e-5e01-c95f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0214 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e67e-5e02-c960-f23c91a70cca . _:0ae0983b-e67e-5e02-c960-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0215 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-15 Heating Valve Output" ; ph:dis "Bravo VAV 2-15 Heating Valve Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e67e-5e03-c961-f23c91a70cca . _:0ae0983b-e67e-5e03-c961-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0216 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-15 Supply Air Temperature" ; ph:dis "Bravo VAV 2-15 Supply Air Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e04-c962-f23c91a70cca . _:0ae0983b-e67e-5e04-c962-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0217 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e05-c963-f23c91a70cca . _:0ae0983b-e67e-5e05-c963-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0218 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Temperature" ; ph:dis "Bravo VAV 2-15 Zone Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e06-c964-f23c91a70cca . _:0ae0983b-e67e-5e06-c964-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0219 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-16" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e67e-5e07-c965-f23c91a70cca . _:0ae0983b-e67e-5e07-c965-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-021a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-16 Damper Output" ; ph:dis "Bravo VAV 2-16 Damper Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e67e-5e08-c966-f23c91a70cca . _:0ae0983b-e67e-5e08-c966-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-021b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e67e-5e09-c967-f23c91a70cca . _:0ae0983b-e67e-5e09-c967-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-021c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e67e-5e0a-c968-f23c91a70cca . _:0ae0983b-e67e-5e0a-c968-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-021d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-16 Heating Valve Output" ; ph:dis "Bravo VAV 2-16 Heating Valve Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e67e-5e0b-c969-f23c91a70cca . _:0ae0983b-e67e-5e0b-c969-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-021e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-16 Supply Air Temperature" ; ph:dis "Bravo VAV 2-16 Supply Air Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e0c-c96a-f23c91a70cca . _:0ae0983b-e67e-5e0c-c96a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-021f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e0d-c96b-f23c91a70cca . _:0ae0983b-e67e-5e0d-c96b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0220 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Temperature" ; ph:dis "Bravo VAV 2-16 Zone Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e67e-5e0e-c96c-f23c91a70cca . _:0ae0983b-e67e-5e0e-c96c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0221 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-17" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e67e-5e0f-c96d-f23c91a70cca . _:0ae0983b-e67e-5e0f-c96d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0222 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-17 Damper Output" ; ph:dis "Bravo VAV 2-17 Damper Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e68d-a040-c96e-f23c91a70cca . _:0ae0983b-e68d-a040-c96e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0223 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e68d-a041-c96f-f23c91a70cca . _:0ae0983b-e68d-a041-c96f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0224 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e68d-a042-c970-f23c91a70cca . _:0ae0983b-e68d-a042-c970-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0225 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-17 Heating Valve Output" ; ph:dis "Bravo VAV 2-17 Heating Valve Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e68d-a043-c971-f23c91a70cca . _:0ae0983b-e68d-a043-c971-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0226 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-17 Supply Air Temperature" ; ph:dis "Bravo VAV 2-17 Supply Air Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a044-c972-f23c91a70cca . _:0ae0983b-e68d-a044-c972-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0227 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a045-c973-f23c91a70cca . _:0ae0983b-e68d-a045-c973-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0228 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Temperature" ; ph:dis "Bravo VAV 2-17 Zone Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a046-c974-f23c91a70cca . _:0ae0983b-e68d-a046-c974-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0229 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-18" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e68d-a047-c975-f23c91a70cca . _:0ae0983b-e68d-a047-c975-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 15 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 550 . _:b-022a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-18 Damper Output" ; ph:dis "Bravo VAV 2-18 Damper Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e68d-a048-c976-f23c91a70cca . _:0ae0983b-e68d-a048-c976-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e68d-a049-c977-f23c91a70cca . _:0ae0983b-e68d-a049-c977-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e68d-a04a-c978-f23c91a70cca . _:0ae0983b-e68d-a04a-c978-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-022d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-18 Heating Valve Output" ; ph:dis "Bravo VAV 2-18 Heating Valve Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e68d-a04b-c979-f23c91a70cca . _:0ae0983b-e68d-a04b-c979-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-022e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-18 Supply Air Temperature" ; ph:dis "Bravo VAV 2-18 Supply Air Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a04c-c97a-f23c91a70cca . _:0ae0983b-e68d-a04c-c97a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-022f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a04d-c97b-f23c91a70cca . _:0ae0983b-e68d-a04d-c97b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0230 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Temperature" ; ph:dis "Bravo VAV 2-18 Zone Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e68d-a04e-c97c-f23c91a70cca . _:0ae0983b-e68d-a04e-c97c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0231 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-19" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e68d-a04f-c97d-f23c91a70cca . _:0ae0983b-e68d-a04f-c97d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0232 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-19 Damper Output" ; ph:dis "Bravo VAV 2-19 Damper Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e68d-a050-c97e-f23c91a70cca . _:0ae0983b-e68d-a050-c97e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0233 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e68d-a051-c97f-f23c91a70cca . _:0ae0983b-e68d-a051-c97f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0234 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e69c-e280-c980-f23c91a70cca . _:0ae0983b-e69c-e280-c980-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0235 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-19 Heating Valve Output" ; ph:dis "Bravo VAV 2-19 Heating Valve Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e69c-e281-c981-f23c91a70cca . _:0ae0983b-e69c-e281-c981-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0236 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-19 Supply Air Temperature" ; ph:dis "Bravo VAV 2-19 Supply Air Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e282-c982-f23c91a70cca . _:0ae0983b-e69c-e282-c982-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0237 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e283-c983-f23c91a70cca . _:0ae0983b-e69c-e283-c983-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0238 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Temperature" ; ph:dis "Bravo VAV 2-19 Zone Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e284-c984-f23c91a70cca . _:0ae0983b-e69c-e284-c984-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0239 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-2" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e69c-e285-c985-f23c91a70cca . _:0ae0983b-e69c-e285-c985-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-023a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-2 Damper Output" ; ph:dis "Bravo VAV 2-2 Damper Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e69c-e286-c986-f23c91a70cca . _:0ae0983b-e69c-e286-c986-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-023b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e69c-e287-c987-f23c91a70cca . _:0ae0983b-e69c-e287-c987-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-023c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e69c-e288-c988-f23c91a70cca . _:0ae0983b-e69c-e288-c988-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-023d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-2 Heating Valve Output" ; ph:dis "Bravo VAV 2-2 Heating Valve Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e69c-e289-c989-f23c91a70cca . _:0ae0983b-e69c-e289-c989-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-023e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-2 Supply Air Temperature" ; ph:dis "Bravo VAV 2-2 Supply Air Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e28a-c98a-f23c91a70cca . _:0ae0983b-e69c-e28a-c98a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-023f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e28b-c98b-f23c91a70cca . _:0ae0983b-e69c-e28b-c98b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0240 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Temperature" ; ph:dis "Bravo VAV 2-2 Zone Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e28c-c98c-f23c91a70cca . _:0ae0983b-e69c-e28c-c98c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0241 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-20" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e69c-e28d-c98d-f23c91a70cca . _:0ae0983b-e69c-e28d-c98d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-0242 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-20 Damper Output" ; ph:dis "Bravo VAV 2-20 Damper Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e69c-e28e-c98e-f23c91a70cca . _:0ae0983b-e69c-e28e-c98e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0243 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e69c-e28f-c98f-f23c91a70cca . _:0ae0983b-e69c-e28f-c98f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0244 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e69c-e290-c990-f23c91a70cca . _:0ae0983b-e69c-e290-c990-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0245 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-20 Heating Valve Output" ; ph:dis "Bravo VAV 2-20 Heating Valve Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e69c-e291-c991-f23c91a70cca . _:0ae0983b-e69c-e291-c991-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0246 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-20 Supply Air Temperature" ; ph:dis "Bravo VAV 2-20 Supply Air Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e69c-e292-c992-f23c91a70cca . _:0ae0983b-e69c-e292-c992-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0247 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6ac-24c0-c993-f23c91a70cca . _:0ae0983b-e6ac-24c0-c993-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0248 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Temperature" ; ph:dis "Bravo VAV 2-20 Zone Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6ac-24c1-c994-f23c91a70cca . _:0ae0983b-e6ac-24c1-c994-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0249 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-21" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6ac-24c2-c995-f23c91a70cca . _:0ae0983b-e6ac-24c2-c995-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 10.4 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-024a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-21 Damper Output" ; ph:dis "Bravo VAV 2-21 Damper Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6ac-24c3-c996-f23c91a70cca . _:0ae0983b-e6ac-24c3-c996-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-024b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6ac-24c4-c997-f23c91a70cca . _:0ae0983b-e6ac-24c4-c997-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-024c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6ac-24c5-c998-f23c91a70cca . _:0ae0983b-e6ac-24c5-c998-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-024d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-21 Heating Valve Output" ; ph:dis "Bravo VAV 2-21 Heating Valve Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6ac-24c6-c999-f23c91a70cca . _:0ae0983b-e6ac-24c6-c999-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-024e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-21 Supply Air Temperature" ; ph:dis "Bravo VAV 2-21 Supply Air Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6ac-24c7-c99a-f23c91a70cca . _:0ae0983b-e6ac-24c7-c99a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-024f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6ac-24c8-c99b-f23c91a70cca . _:0ae0983b-e6ac-24c8-c99b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0250 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Temperature" ; ph:dis "Bravo VAV 2-21 Zone Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6d9-eb80-c99c-f23c91a70cca . _:0ae0983b-e6d9-eb80-c99c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0251 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-22" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6d9-eb81-c99d-f23c91a70cca . _:0ae0983b-e6d9-eb81-c99d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0252 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-22 Damper Output" ; ph:dis "Bravo VAV 2-22 Damper Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6d9-eb82-c99e-f23c91a70cca . _:0ae0983b-e6d9-eb82-c99e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0253 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6e9-2dc0-c99f-f23c91a70cca . _:0ae0983b-e6e9-2dc0-c99f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0254 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6e9-2dc1-c9a0-f23c91a70cca . _:0ae0983b-e6e9-2dc1-c9a0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0255 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-22 Heating Valve Output" ; ph:dis "Bravo VAV 2-22 Heating Valve Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6e9-2dc2-c9a1-f23c91a70cca . _:0ae0983b-e6e9-2dc2-c9a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0256 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-22 Supply Air Temperature" ; ph:dis "Bravo VAV 2-22 Supply Air Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dc3-c9a2-f23c91a70cca . _:0ae0983b-e6e9-2dc3-c9a2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0257 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dc4-c9a3-f23c91a70cca . _:0ae0983b-e6e9-2dc4-c9a3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0258 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Temperature" ; ph:dis "Bravo VAV 2-22 Zone Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dc5-c9a4-f23c91a70cca . _:0ae0983b-e6e9-2dc5-c9a4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0259 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-23" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6e9-2dc6-c9a5-f23c91a70cca . _:0ae0983b-e6e9-2dc6-c9a5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-025a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-23 Damper Output" ; ph:dis "Bravo VAV 2-23 Damper Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6e9-2dc7-c9a6-f23c91a70cca . _:0ae0983b-e6e9-2dc7-c9a6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-025b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6e9-2dc8-c9a7-f23c91a70cca . _:0ae0983b-e6e9-2dc8-c9a7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-025c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6e9-2dc9-c9a8-f23c91a70cca . _:0ae0983b-e6e9-2dc9-c9a8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-025d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-23 Heating Valve Output" ; ph:dis "Bravo VAV 2-23 Heating Valve Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6e9-2dca-c9a9-f23c91a70cca . _:0ae0983b-e6e9-2dca-c9a9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-025e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-23 Supply Air Temperature" ; ph:dis "Bravo VAV 2-23 Supply Air Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dcb-c9aa-f23c91a70cca . _:0ae0983b-e6e9-2dcb-c9aa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-025f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dcc-c9ab-f23c91a70cca . _:0ae0983b-e6e9-2dcc-c9ab-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0260 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Temperature" ; ph:dis "Bravo VAV 2-23 Zone Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6e9-2dcd-c9ac-f23c91a70cca . _:0ae0983b-e6e9-2dcd-c9ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0261 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-24" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6f8-7000-c9ad-f23c91a70cca . _:0ae0983b-e6f8-7000-c9ad-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 15.4 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1600 . _:b-0262 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-24 Damper Output" ; ph:dis "Bravo VAV 2-24 Damper Output" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6f8-7001-c9ae-f23c91a70cca . _:0ae0983b-e6f8-7001-c9ae-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0263 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6f8-7002-c9af-f23c91a70cca . _:0ae0983b-e6f8-7002-c9af-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0264 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6f8-7003-c9b0-f23c91a70cca . _:0ae0983b-e6f8-7003-c9b0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0265 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-24 Heating Valve" ; ph:dis "Bravo VAV 2-24 Heating Valve" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6f8-7004-c9b1-f23c91a70cca . _:0ae0983b-e6f8-7004-c9b1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0266 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-24 Supply Air Temperature" ; ph:dis "Bravo VAV 2-24 Supply Air Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-7005-c9b2-f23c91a70cca . _:0ae0983b-e6f8-7005-c9b2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0267 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-7006-c9b3-f23c91a70cca . _:0ae0983b-e6f8-7006-c9b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0268 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Temperature" ; ph:dis "Bravo VAV 2-24 Zone Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-7007-c9b4-f23c91a70cca . _:0ae0983b-e6f8-7007-c9b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0269 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-25" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6f8-7008-c9b5-f23c91a70cca . _:0ae0983b-e6f8-7008-c9b5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-026a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-25 Damper Output" ; ph:dis "Bravo VAV 2-25 Damper Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6f8-7009-c9b6-f23c91a70cca . _:0ae0983b-e6f8-7009-c9b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-026b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6f8-700a-c9b7-f23c91a70cca . _:0ae0983b-e6f8-700a-c9b7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-026c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6f8-700b-c9b8-f23c91a70cca . _:0ae0983b-e6f8-700b-c9b8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-026d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-25 Heating Valve Output" ; ph:dis "Bravo VAV 2-25 Heating Valve Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6f8-700c-c9b9-f23c91a70cca . _:0ae0983b-e6f8-700c-c9b9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-026e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-25 Supply Air Temperature" ; ph:dis "Bravo VAV 2-25 Supply Air Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-700d-c9ba-f23c91a70cca . _:0ae0983b-e6f8-700d-c9ba-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-026f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-700e-c9bb-f23c91a70cca . _:0ae0983b-e6f8-700e-c9bb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0270 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Temperature" ; ph:dis "Bravo VAV 2-25 Zone Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e6f8-700f-c9bc-f23c91a70cca . _:0ae0983b-e6f8-700f-c9bc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0271 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-26" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e6f8-7010-c9bd-f23c91a70cca . _:0ae0983b-e6f8-7010-c9bd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 300 . _:b-0272 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-26 Damper Output" ; ph:dis "Bravo VAV 2-26 Damper Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e6f8-7011-c9be-f23c91a70cca . _:0ae0983b-e6f8-7011-c9be-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0273 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e6f8-7012-c9bf-f23c91a70cca . _:0ae0983b-e6f8-7012-c9bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0274 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e707-b240-c9c0-f23c91a70cca . _:0ae0983b-e707-b240-c9c0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0275 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-26 Heating Valve Output" ; ph:dis "Bravo VAV 2-26 Heating Valve Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e707-b241-c9c1-f23c91a70cca . _:0ae0983b-e707-b241-c9c1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0276 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-26 Supply Air Temperature" ; ph:dis "Bravo VAV 2-26 Supply Air Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b242-c9c2-f23c91a70cca . _:0ae0983b-e707-b242-c9c2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0277 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b243-c9c3-f23c91a70cca . _:0ae0983b-e707-b243-c9c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0278 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Temperature" ; ph:dis "Bravo VAV 2-26 Zone Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b244-c9c4-f23c91a70cca . _:0ae0983b-e707-b244-c9c4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0279 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-27" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e707-b245-c9c5-f23c91a70cca . _:0ae0983b-e707-b245-c9c5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 1125 . _:b-027a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-27 Damper Output" ; ph:dis "Bravo VAV 2-27 Damper Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e707-b246-c9c6-f23c91a70cca . _:0ae0983b-e707-b246-c9c6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-027b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e707-b247-c9c7-f23c91a70cca . _:0ae0983b-e707-b247-c9c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e707-b248-c9c8-f23c91a70cca . _:0ae0983b-e707-b248-c9c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-27 Heating Valve Output" ; ph:dis "Bravo VAV 2-27 Heating Valve Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e707-b249-c9c9-f23c91a70cca . _:0ae0983b-e707-b249-c9c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-027e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-27 Supply Air Temperature" ; ph:dis "Bravo VAV 2-27 Supply Air Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b24a-c9ca-f23c91a70cca . _:0ae0983b-e707-b24a-c9ca-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-027f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b24b-c9cb-f23c91a70cca . _:0ae0983b-e707-b24b-c9cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0280 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Temperature" ; ph:dis "Bravo VAV 2-27 Zone Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b24c-c9cc-f23c91a70cca . _:0ae0983b-e707-b24c-c9cc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0281 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-28" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e707-b24d-c9cd-f23c91a70cca . _:0ae0983b-e707-b24d-c9cd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0282 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-28 Damper Output" ; ph:dis "Bravo VAV 2-28 Damper Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e707-b24e-c9ce-f23c91a70cca . _:0ae0983b-e707-b24e-c9ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0283 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e707-b24f-c9cf-f23c91a70cca . _:0ae0983b-e707-b24f-c9cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0284 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e707-b250-c9d0-f23c91a70cca . _:0ae0983b-e707-b250-c9d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0285 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-28 Heating Valve Output" ; ph:dis "Bravo VAV 2-28 Heating Valve Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e707-b251-c9d1-f23c91a70cca . _:0ae0983b-e707-b251-c9d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0286 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-28 Supply Air Temperature" ; ph:dis "Bravo VAV 2-28 Supply Air Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e707-b252-c9d2-f23c91a70cca . _:0ae0983b-e707-b252-c9d2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0287 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e716-f480-c9d3-f23c91a70cca . _:0ae0983b-e716-f480-c9d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0288 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Temperature" ; ph:dis "Bravo VAV 2-28 Zone Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e716-f481-c9d4-f23c91a70cca . _:0ae0983b-e716-f481-c9d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0289 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-29" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-29" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e744-bb40-c9d5-f23c91a70cca . _:0ae0983b-e744-bb40-c9d5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-028a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-29 Damper Output" ; ph:dis "Bravo VAV 2-29 Damper Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e744-bb41-c9d6-f23c91a70cca . _:0ae0983b-e744-bb41-c9d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-028b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e744-bb42-c9d7-f23c91a70cca . _:0ae0983b-e744-bb42-c9d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-028c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e744-bb43-c9d8-f23c91a70cca . _:0ae0983b-e744-bb43-c9d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-028d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-29 Heating Valve Output" ; ph:dis "Bravo VAV 2-29 Heating Valve Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e744-bb44-c9d9-f23c91a70cca . _:0ae0983b-e744-bb44-c9d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-028e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-29 Supply Air Temperature" ; ph:dis "Bravo VAV 2-29 Supply Air Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e744-bb45-c9da-f23c91a70cca . _:0ae0983b-e744-bb45-c9da-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-028f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-29 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e744-bb46-c9db-f23c91a70cca . _:0ae0983b-e744-bb46-c9db-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0290 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Temperature" ; ph:dis "Bravo VAV 2-29 Zone Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e744-bb47-c9dc-f23c91a70cca . _:0ae0983b-e744-bb47-c9dc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0291 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-3" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e744-bb48-c9dd-f23c91a70cca . _:0ae0983b-e744-bb48-c9dd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0292 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-3 Damper Output" ; ph:dis "Bravo VAV 2-3 Damper Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e753-fd80-c9de-f23c91a70cca . _:0ae0983b-e753-fd80-c9de-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0293 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd81-c9df-f23c91a70cca . _:0ae0983b-e753-fd81-c9df-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0294 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd82-c9e0-f23c91a70cca . _:0ae0983b-e753-fd82-c9e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0295 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-3 Heating Valve Output" ; ph:dis "Bravo VAV 2-3 Heating Valve Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e753-fd83-c9e1-f23c91a70cca . _:0ae0983b-e753-fd83-c9e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0296 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-3 Supply Air Temperature" ; ph:dis "Bravo VAV 2-3 Supply Air Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd84-c9e2-f23c91a70cca . _:0ae0983b-e753-fd84-c9e2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0297 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd85-c9e3-f23c91a70cca . _:0ae0983b-e753-fd85-c9e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0298 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Temperature" ; ph:dis "Bravo VAV 2-3 Zone Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd86-c9e4-f23c91a70cca . _:0ae0983b-e753-fd86-c9e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0299 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-30" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-30" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e753-fd87-c9e5-f23c91a70cca . _:0ae0983b-e753-fd87-c9e5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-029a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-30 Damper Output" ; ph:dis "Bravo VAV 2-30 Damper Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e753-fd88-c9e6-f23c91a70cca . _:0ae0983b-e753-fd88-c9e6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-029b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd89-c9e7-f23c91a70cca . _:0ae0983b-e753-fd89-c9e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-029c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd8a-c9e8-f23c91a70cca . _:0ae0983b-e753-fd8a-c9e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-029d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-30 Heating Valve Output" ; ph:dis "Bravo VAV 2-30 Heating Valve Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e753-fd8b-c9e9-f23c91a70cca . _:0ae0983b-e753-fd8b-c9e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-029e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-30 Supply Air Temperature" ; ph:dis "Bravo VAV 2-30 Supply Air Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd8c-c9ea-f23c91a70cca . _:0ae0983b-e753-fd8c-c9ea-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-029f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-30 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd8d-c9eb-f23c91a70cca . _:0ae0983b-e753-fd8d-c9eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Temperature" ; ph:dis "Bravo VAV 2-30 Zone Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e753-fd8e-c9ec-f23c91a70cca . _:0ae0983b-e753-fd8e-c9ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-31" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-31" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e753-fd8f-c9ed-f23c91a70cca . _:0ae0983b-e753-fd8f-c9ed-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 650 . _:b-02a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-31 Damper Output" ; ph:dis "Bravo VAV 2-31 Damper Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e753-fd90-c9ee-f23c91a70cca . _:0ae0983b-e753-fd90-c9ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd91-c9ef-f23c91a70cca . _:0ae0983b-e753-fd91-c9ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e753-fd92-c9f0-f23c91a70cca . _:0ae0983b-e753-fd92-c9f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-31 Heating Valve Output" ; ph:dis "Bravo VAV 2-31 Heating Valve Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e763-3fc0-c9f1-f23c91a70cca . _:0ae0983b-e763-3fc0-c9f1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-31 Supply Air Temperature" ; ph:dis "Bravo VAV 2-31 Supply Air Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fc1-c9f2-f23c91a70cca . _:0ae0983b-e763-3fc1-c9f2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-31 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fc2-c9f3-f23c91a70cca . _:0ae0983b-e763-3fc2-c9f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Temperature" ; ph:dis "Bravo VAV 2-31 Zone Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fc3-c9f4-f23c91a70cca . _:0ae0983b-e763-3fc3-c9f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-32" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-32" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e763-3fc4-c9f5-f23c91a70cca . _:0ae0983b-e763-3fc4-c9f5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 28.6 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 2150 . _:b-02aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-32 Damper Output" ; ph:dis "Bravo VAV 2-32 Damper Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e763-3fc5-c9f6-f23c91a70cca . _:0ae0983b-e763-3fc5-c9f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e763-3fc6-c9f7-f23c91a70cca . _:0ae0983b-e763-3fc6-c9f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e763-3fc7-c9f8-f23c91a70cca . _:0ae0983b-e763-3fc7-c9f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-32 Heating Valve Output" ; ph:dis "Bravo VAV 2-32 Heating Valve Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e763-3fc8-c9f9-f23c91a70cca . _:0ae0983b-e763-3fc8-c9f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-32 Supply Air Temperature" ; ph:dis "Bravo VAV 2-32 Supply Air Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fc9-c9fa-f23c91a70cca . _:0ae0983b-e763-3fc9-c9fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-32 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fca-c9fb-f23c91a70cca . _:0ae0983b-e763-3fca-c9fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Temperature" ; ph:dis "Bravo VAV 2-32 Zone Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fcb-c9fc-f23c91a70cca . _:0ae0983b-e763-3fcb-c9fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-33" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-33" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e763-3fcc-c9fd-f23c91a70cca . _:0ae0983b-e763-3fcc-c9fd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-02b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-33 Damper Output" ; ph:dis "Bravo VAV 2-33 Damper Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e763-3fcd-c9fe-f23c91a70cca . _:0ae0983b-e763-3fcd-c9fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e763-3fce-c9ff-f23c91a70cca . _:0ae0983b-e763-3fce-c9ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e763-3fcf-ca00-f23c91a70cca . _:0ae0983b-e763-3fcf-ca00-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-33 Heating Valve Output" ; ph:dis "Bravo VAV 2-33 Heating Valve Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e763-3fd0-ca01-f23c91a70cca . _:0ae0983b-e763-3fd0-ca01-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-33 Supply Air Temperature" ; ph:dis "Bravo VAV 2-33 Supply Air Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fd1-ca02-f23c91a70cca . _:0ae0983b-e763-3fd1-ca02-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-33 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e763-3fd2-ca03-f23c91a70cca . _:0ae0983b-e763-3fd2-ca03-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Temperature" ; ph:dis "Bravo VAV 2-33 Zone Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e772-8200-ca04-f23c91a70cca . _:0ae0983b-e772-8200-ca04-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-34" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-34" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e772-8201-ca05-f23c91a70cca . _:0ae0983b-e772-8201-ca05-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 10.3 ; _:designHotWaterFlow 1 ; _:designAirFlow 575 . _:b-02ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-34 Damper Output" ; ph:dis "Bravo VAV 2-34 Damper Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e772-8202-ca06-f23c91a70cca . _:0ae0983b-e772-8202-ca06-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e772-8203-ca07-f23c91a70cca . _:0ae0983b-e772-8203-ca07-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e772-8204-ca08-f23c91a70cca . _:0ae0983b-e772-8204-ca08-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-34 Heating Valve Output" ; ph:dis "Bravo VAV 2-34 Heating Valve Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e772-8205-ca09-f23c91a70cca . _:0ae0983b-e772-8205-ca09-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-34 Supply Air Temperature" ; ph:dis "Bravo VAV 2-34 Supply Air Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e772-8206-ca0a-f23c91a70cca . _:0ae0983b-e772-8206-ca0a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-34 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e772-8207-ca0b-f23c91a70cca . _:0ae0983b-e772-8207-ca0b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Temperature" ; ph:dis "Bravo VAV 2-34 Zone Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e772-8208-ca0c-f23c91a70cca . _:0ae0983b-e772-8208-ca0c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-35" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-35" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e772-8209-ca0d-f23c91a70cca . _:0ae0983b-e772-8209-ca0d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-35 Damper Output" ; ph:dis "Bravo VAV 2-35 Damper Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e772-820a-ca0e-f23c91a70cca . _:0ae0983b-e772-820a-ca0e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e772-820b-ca0f-f23c91a70cca . _:0ae0983b-e772-820b-ca0f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-02c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7af-8b00-ca10-f23c91a70cca . _:0ae0983b-e7af-8b00-ca10-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-35 Heating Valve Output" ; ph:dis "Bravo VAV 2-35 Heating Valve Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7af-8b01-ca11-f23c91a70cca . _:0ae0983b-e7af-8b01-ca11-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-35 Supply Air Temperature" ; ph:dis "Bravo VAV 2-35 Supply Air Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b02-ca12-f23c91a70cca . _:0ae0983b-e7af-8b02-ca12-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-35 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b03-ca13-f23c91a70cca . _:0ae0983b-e7af-8b03-ca13-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Temperature" ; ph:dis "Bravo VAV 2-35 Zone Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b04-ca14-f23c91a70cca . _:0ae0983b-e7af-8b04-ca14-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-36" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-36" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7af-8b05-ca15-f23c91a70cca . _:0ae0983b-e7af-8b05-ca15-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-02ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-36 Damper Output" ; ph:dis "Bravo VAV 2-36 Damper Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7af-8b06-ca16-f23c91a70cca . _:0ae0983b-e7af-8b06-ca16-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7af-8b07-ca17-f23c91a70cca . _:0ae0983b-e7af-8b07-ca17-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-02cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7af-8b08-ca18-f23c91a70cca . _:0ae0983b-e7af-8b08-ca18-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-36 Heating Valve Output" ; ph:dis "Bravo VAV 2-36 Heating Valve Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7af-8b09-ca19-f23c91a70cca . _:0ae0983b-e7af-8b09-ca19-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-36 Supply Air Temperature" ; ph:dis "Bravo VAV 2-36 Supply Air Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b0a-ca1a-f23c91a70cca . _:0ae0983b-e7af-8b0a-ca1a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-36 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b0b-ca1b-f23c91a70cca . _:0ae0983b-e7af-8b0b-ca1b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Temperature" ; ph:dis "Bravo VAV 2-36 Zone Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7af-8b0c-ca1c-f23c91a70cca . _:0ae0983b-e7af-8b0c-ca1c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-37" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-37" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7af-8b0d-ca1d-f23c91a70cca . _:0ae0983b-e7af-8b0d-ca1d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 500 . _:b-02d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-37 Damper Output" ; ph:dis "Bravo VAV 2-37 Damper Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7af-8b0e-ca1e-f23c91a70cca . _:0ae0983b-e7af-8b0e-ca1e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd40-ca1f-f23c91a70cca . _:0ae0983b-e7be-cd40-ca1f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd41-ca20-f23c91a70cca . _:0ae0983b-e7be-cd41-ca20-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-37 Heating Valve Output" ; ph:dis "Bravo VAV 2-37 Heating Valve Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7be-cd42-ca21-f23c91a70cca . _:0ae0983b-e7be-cd42-ca21-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-37 Supply Air Temperature" ; ph:dis "Bravo VAV 2-37 Supply Air Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd43-ca22-f23c91a70cca . _:0ae0983b-e7be-cd43-ca22-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-37 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd44-ca23-f23c91a70cca . _:0ae0983b-e7be-cd44-ca23-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Temperature" ; ph:dis "Bravo VAV 2-37 Zone Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd45-ca24-f23c91a70cca . _:0ae0983b-e7be-cd45-ca24-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-38" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-38" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7be-cd46-ca25-f23c91a70cca . _:0ae0983b-e7be-cd46-ca25-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-38 Damper Output" ; ph:dis "Bravo VAV 2-38 Damper Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7be-cd47-ca26-f23c91a70cca . _:0ae0983b-e7be-cd47-ca26-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd48-ca27-f23c91a70cca . _:0ae0983b-e7be-cd48-ca27-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd49-ca28-f23c91a70cca . _:0ae0983b-e7be-cd49-ca28-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-38 Heating Valve Output" ; ph:dis "Bravo VAV 2-38 Heating Valve Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7be-cd4a-ca29-f23c91a70cca . _:0ae0983b-e7be-cd4a-ca29-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-38 Supply Air Temperature" ; ph:dis "Bravo VAV 2-38 Supply Air Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd4b-ca2a-f23c91a70cca . _:0ae0983b-e7be-cd4b-ca2a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-38 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd4c-ca2b-f23c91a70cca . _:0ae0983b-e7be-cd4c-ca2b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Temperature" ; ph:dis "Bravo VAV 2-38 Zone Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7be-cd4d-ca2c-f23c91a70cca . _:0ae0983b-e7be-cd4d-ca2c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-39" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-39" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7be-cd4e-ca2d-f23c91a70cca . _:0ae0983b-e7be-cd4e-ca2d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 9.5 ; _:designAirFlow 475 . _:b-02e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-39 Damper Output" ; ph:dis "Bravo VAV 2-39 Damper Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7be-cd4f-ca2e-f23c91a70cca . _:0ae0983b-e7be-cd4f-ca2e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd50-ca2f-f23c91a70cca . _:0ae0983b-e7be-cd50-ca2f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7be-cd51-ca30-f23c91a70cca . _:0ae0983b-e7be-cd51-ca30-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-39 Heating Valve Output" ; ph:dis "Bravo VAV 2-39 Heating Valve Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7be-cd52-ca31-f23c91a70cca . _:0ae0983b-e7be-cd52-ca31-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-39 Supply Air Temperature" ; ph:dis "Bravo VAV 2-39 Supply Air Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f80-ca32-f23c91a70cca . _:0ae0983b-e7ce-0f80-ca32-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-39 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f81-ca33-f23c91a70cca . _:0ae0983b-e7ce-0f81-ca33-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Temperature" ; ph:dis "Bravo VAV 2-39 Zone Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f82-ca34-f23c91a70cca . _:0ae0983b-e7ce-0f82-ca34-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-4" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7ce-0f83-ca35-f23c91a70cca . _:0ae0983b-e7ce-0f83-ca35-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-02ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-4 Damper Output" ; ph:dis "Bravo VAV 2-4 Damper Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7ce-0f84-ca36-f23c91a70cca . _:0ae0983b-e7ce-0f84-ca36-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7ce-0f85-ca37-f23c91a70cca . _:0ae0983b-e7ce-0f85-ca37-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7ce-0f86-ca38-f23c91a70cca . _:0ae0983b-e7ce-0f86-ca38-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-4 Heating Valve Output" ; ph:dis "Bravo VAV 2-4 Heating Valve Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7ce-0f87-ca39-f23c91a70cca . _:0ae0983b-e7ce-0f87-ca39-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-4 Supply Air Temperature" ; ph:dis "Bravo VAV 2-4 Supply Air Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f88-ca3a-f23c91a70cca . _:0ae0983b-e7ce-0f88-ca3a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f89-ca3b-f23c91a70cca . _:0ae0983b-e7ce-0f89-ca3b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Temperature" ; ph:dis "Bravo VAV 2-4 Zone Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f8a-ca3c-f23c91a70cca . _:0ae0983b-e7ce-0f8a-ca3c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-40" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-40" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7ce-0f8b-ca3d-f23c91a70cca . _:0ae0983b-e7ce-0f8b-ca3d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-40 Damper Output" ; ph:dis "Bravo VAV 2-40 Damper Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7ce-0f8c-ca3e-f23c91a70cca . _:0ae0983b-e7ce-0f8c-ca3e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7ce-0f8d-ca3f-f23c91a70cca . _:0ae0983b-e7ce-0f8d-ca3f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7ce-0f8e-ca40-f23c91a70cca . _:0ae0983b-e7ce-0f8e-ca40-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-40 Heating Valve Output" ; ph:dis "Bravo VAV 2-40 Heating Valve Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7ce-0f8f-ca41-f23c91a70cca . _:0ae0983b-e7ce-0f8f-ca41-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-40 Supply Air Temperature" ; ph:dis "Bravo VAV 2-40 Supply Air Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f90-ca42-f23c91a70cca . _:0ae0983b-e7ce-0f90-ca42-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-40 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f91-ca43-f23c91a70cca . _:0ae0983b-e7ce-0f91-ca43-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Temperature" ; ph:dis "Bravo VAV 2-40 Zone Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7ce-0f92-ca44-f23c91a70cca . _:0ae0983b-e7ce-0f92-ca44-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-41" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-41" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7dd-51c0-ca45-f23c91a70cca . _:0ae0983b-e7dd-51c0-ca45-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-41 Damper Output" ; ph:dis "Bravo VAV 2-41 Damper Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7dd-51c1-ca46-f23c91a70cca . _:0ae0983b-e7dd-51c1-ca46-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.626-04:00"^^xsd:dateTime . _:b-02fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7dd-51c2-ca47-f23c91a70cca . _:0ae0983b-e7dd-51c2-ca47-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e7dd-51c3-ca48-f23c91a70cca . _:0ae0983b-e7dd-51c3-ca48-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-41 Heating Valve Output" ; ph:dis "Bravo VAV 2-41 Heating Valve Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e7dd-51c4-ca49-f23c91a70cca . _:0ae0983b-e7dd-51c4-ca49-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-41 Supply Air Temperature" ; ph:dis "Bravo VAV 2-41 Supply Air Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7dd-51c5-ca4a-f23c91a70cca . _:0ae0983b-e7dd-51c5-ca4a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-41 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7dd-51c6-ca4b-f23c91a70cca . _:0ae0983b-e7dd-51c6-ca4b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0300 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Temperature" ; ph:dis "Bravo VAV 2-41 Zone Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e7dd-51c7-ca4c-f23c91a70cca . _:0ae0983b-e7dd-51c7-ca4c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0301 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-42" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-42" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e7dd-51c8-ca4d-f23c91a70cca . _:0ae0983b-e7dd-51c8-ca4d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0302 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-42 Damper Output" ; ph:dis "Bravo VAV 2-42 Damper Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e80b-1880-ca4e-f23c91a70cca . _:0ae0983b-e80b-1880-ca4e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0303 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e80b-1881-ca4f-f23c91a70cca . _:0ae0983b-e80b-1881-ca4f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0304 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e81a-5ac0-ca50-f23c91a70cca . _:0ae0983b-e81a-5ac0-ca50-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0305 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-42 Heating Valve Output" ; ph:dis "Bravo VAV 2-42 Heating Valve Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e81a-5ac1-ca51-f23c91a70cca . _:0ae0983b-e81a-5ac1-ca51-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0306 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-42 Supply Air Temperature" ; ph:dis "Bravo VAV 2-42 Supply Air Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e81a-5ac2-ca52-f23c91a70cca . _:0ae0983b-e81a-5ac2-ca52-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0307 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-42 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e81a-5ac3-ca53-f23c91a70cca . _:0ae0983b-e81a-5ac3-ca53-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0308 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Temperature" ; ph:dis "Bravo VAV 2-42 Zone Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e81a-5ac4-ca54-f23c91a70cca . _:0ae0983b-e81a-5ac4-ca54-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0309 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-43" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-43" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e81a-5ac5-ca55-f23c91a70cca . _:0ae0983b-e81a-5ac5-ca55-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 141 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-030a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-43 Damper Output" ; ph:dis "Bravo VAV 2-43 Damper Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e81a-5ac6-ca56-f23c91a70cca . _:0ae0983b-e81a-5ac6-ca56-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-030b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e81a-5ac7-ca57-f23c91a70cca . _:0ae0983b-e81a-5ac7-ca57-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e81a-5ac8-ca58-f23c91a70cca . _:0ae0983b-e81a-5ac8-ca58-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-030d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-43 Heating Valve Output" ; ph:dis "Bravo VAV 2-43 Heating Valve Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e81a-5ac9-ca59-f23c91a70cca . _:0ae0983b-e81a-5ac9-ca59-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-030e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-43 Supply Air Temperature" ; ph:dis "Bravo VAV 2-43 Supply Air Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e81a-5aca-ca5a-f23c91a70cca . _:0ae0983b-e81a-5aca-ca5a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-43 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e81a-5acb-ca5b-f23c91a70cca . _:0ae0983b-e81a-5acb-ca5b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0310 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Temperature" ; ph:dis "Bravo VAV 2-43 Zone Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e848-2180-ca5c-f23c91a70cca . _:0ae0983b-e848-2180-ca5c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0311 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-44" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-44" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e848-2181-ca5d-f23c91a70cca . _:0ae0983b-e848-2181-ca5d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0312 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-44 Damper Output" ; ph:dis "Bravo VAV 2-44 Damper Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e848-2182-ca5e-f23c91a70cca . _:0ae0983b-e848-2182-ca5e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0313 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e848-2183-ca5f-f23c91a70cca . _:0ae0983b-e848-2183-ca5f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0314 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e848-2184-ca60-f23c91a70cca . _:0ae0983b-e848-2184-ca60-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0315 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-44 Heating Valve Output" ; ph:dis "Bravo VAV 2-44 Heating Valve Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e848-2185-ca61-f23c91a70cca . _:0ae0983b-e848-2185-ca61-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0316 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-44 Supply Air Temperature" ; ph:dis "Bravo VAV 2-44 Supply Air Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e848-2186-ca62-f23c91a70cca . _:0ae0983b-e848-2186-ca62-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0317 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-44 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e848-2187-ca63-f23c91a70cca . _:0ae0983b-e848-2187-ca63-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0318 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Temperature" ; ph:dis "Bravo VAV 2-44 Zone Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e848-2188-ca64-f23c91a70cca . _:0ae0983b-e848-2188-ca64-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0319 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-45" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-45" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e848-2189-ca65-f23c91a70cca . _:0ae0983b-e848-2189-ca65-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.8 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 600 . _:b-031a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-45 Damper Output" ; ph:dis "Bravo VAV 2-45 Damper Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e848-218a-ca66-f23c91a70cca . _:0ae0983b-e848-218a-ca66-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e848-218b-ca67-f23c91a70cca . _:0ae0983b-e848-218b-ca67-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-031c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e848-218c-ca68-f23c91a70cca . _:0ae0983b-e848-218c-ca68-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-45 Heating Valve Output" ; ph:dis "Bravo VAV 2-45 Heating Valve Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e848-218d-ca69-f23c91a70cca . _:0ae0983b-e848-218d-ca69-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-031e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-45 Supply Air Temperature" ; ph:dis "Bravo VAV 2-45 Supply Air Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e848-218e-ca6a-f23c91a70cca . _:0ae0983b-e848-218e-ca6a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-031f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-45 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63c0-ca6b-f23c91a70cca . _:0ae0983b-e857-63c0-ca6b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0320 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Temperature" ; ph:dis "Bravo VAV 2-45 Zone Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63c1-ca6c-f23c91a70cca . _:0ae0983b-e857-63c1-ca6c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0321 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-46" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-46" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e857-63c2-ca6d-f23c91a70cca . _:0ae0983b-e857-63c2-ca6d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0322 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-46 Damper Output" ; ph:dis "Bravo VAV 2-46 Damper Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e857-63c3-ca6e-f23c91a70cca . _:0ae0983b-e857-63c3-ca6e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0323 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e857-63c4-ca6f-f23c91a70cca . _:0ae0983b-e857-63c4-ca6f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0324 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e857-63c5-ca70-f23c91a70cca . _:0ae0983b-e857-63c5-ca70-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0325 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-46 Heating Valve Output" ; ph:dis "Bravo VAV 2-46 Heating Valve Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e857-63c6-ca71-f23c91a70cca . _:0ae0983b-e857-63c6-ca71-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0326 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-46 Supply Air Temperature" ; ph:dis "Bravo VAV 2-46 Supply Air Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63c7-ca72-f23c91a70cca . _:0ae0983b-e857-63c7-ca72-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0327 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-46 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63c8-ca73-f23c91a70cca . _:0ae0983b-e857-63c8-ca73-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0328 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Temperature" ; ph:dis "Bravo VAV 2-46 Zone Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63c9-ca74-f23c91a70cca . _:0ae0983b-e857-63c9-ca74-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0329 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-47" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-47" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e857-63ca-ca75-f23c91a70cca . _:0ae0983b-e857-63ca-ca75-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 25.9 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1400 . _:b-032a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-47 Damper Output" ; ph:dis "Bravo VAV 2-47 Damper Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e857-63cb-ca76-f23c91a70cca . _:0ae0983b-e857-63cb-ca76-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-032b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e857-63cc-ca77-f23c91a70cca . _:0ae0983b-e857-63cc-ca77-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-032c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e857-63cd-ca78-f23c91a70cca . _:0ae0983b-e857-63cd-ca78-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-47 Heating Valve Output" ; ph:dis "Bravo VAV 2-47 Heating Valve Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e857-63ce-ca79-f23c91a70cca . _:0ae0983b-e857-63ce-ca79-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-47 Supply Air Temperature" ; ph:dis "Bravo VAV 2-47 Supply Air Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63cf-ca7a-f23c91a70cca . _:0ae0983b-e857-63cf-ca7a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-032f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-47 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63d0-ca7b-f23c91a70cca . _:0ae0983b-e857-63d0-ca7b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0330 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Temperature" ; ph:dis "Bravo VAV 2-47 Zone Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e857-63d1-ca7c-f23c91a70cca . _:0ae0983b-e857-63d1-ca7c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0331 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-48" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-48" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e857-63d2-ca7d-f23c91a70cca . _:0ae0983b-e857-63d2-ca7d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0332 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-48 Damper Output" ; ph:dis "Bravo VAV 2-48 Damper Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e866-a600-ca7e-f23c91a70cca . _:0ae0983b-e866-a600-ca7e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0333 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a601-ca7f-f23c91a70cca . _:0ae0983b-e866-a601-ca7f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0334 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a602-ca80-f23c91a70cca . _:0ae0983b-e866-a602-ca80-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0335 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-48 Heating Valve Output" ; ph:dis "Bravo VAV 2-48 Heating Valve Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e866-a603-ca81-f23c91a70cca . _:0ae0983b-e866-a603-ca81-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0336 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-48 Supply Air Temperature" ; ph:dis "Bravo VAV 2-48 Supply Air Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a604-ca82-f23c91a70cca . _:0ae0983b-e866-a604-ca82-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0337 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-48 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a605-ca83-f23c91a70cca . _:0ae0983b-e866-a605-ca83-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0338 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Temperature" ; ph:dis "Bravo VAV 2-48 Zone Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a606-ca84-f23c91a70cca . _:0ae0983b-e866-a606-ca84-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0339 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-49" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-49" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e866-a607-ca85-f23c91a70cca . _:0ae0983b-e866-a607-ca85-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-033a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-49 Damper Output" ; ph:dis "Bravo VAV 2-49 Damper Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e866-a608-ca86-f23c91a70cca . _:0ae0983b-e866-a608-ca86-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-033b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a609-ca87-f23c91a70cca . _:0ae0983b-e866-a609-ca87-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-033c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a60a-ca88-f23c91a70cca . _:0ae0983b-e866-a60a-ca88-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-033d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-49 Heating Valve Output" ; ph:dis "Bravo VAV 2-49 Heating Valve Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e866-a60b-ca89-f23c91a70cca . _:0ae0983b-e866-a60b-ca89-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-033e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-49 Supply Air Temperature" ; ph:dis "Bravo VAV 2-49 Supply Air Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a60c-ca8a-f23c91a70cca . _:0ae0983b-e866-a60c-ca8a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-033f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-49 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a60d-ca8b-f23c91a70cca . _:0ae0983b-e866-a60d-ca8b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0340 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Temperature" ; ph:dis "Bravo VAV 2-49 Zone Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e866-a60e-ca8c-f23c91a70cca . _:0ae0983b-e866-a60e-ca8c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0341 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-5" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e866-a60f-ca8d-f23c91a70cca . _:0ae0983b-e866-a60f-ca8d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0342 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-5 Damper Output" ; ph:dis "Bravo VAV 2-5 Damper Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e866-a610-ca8e-f23c91a70cca . _:0ae0983b-e866-a610-ca8e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0343 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a611-ca8f-f23c91a70cca . _:0ae0983b-e866-a611-ca8f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0344 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e866-a612-ca90-f23c91a70cca . _:0ae0983b-e866-a612-ca90-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0345 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-5 Heating Valve Output" ; ph:dis "Bravo VAV 2-5 Heating Valve Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e875-e840-ca91-f23c91a70cca . _:0ae0983b-e875-e840-ca91-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0346 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-5 Supply Air Temperature" ; ph:dis "Bravo VAV 2-5 Supply Air Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e875-e841-ca92-f23c91a70cca . _:0ae0983b-e875-e841-ca92-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0347 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e875-e842-ca93-f23c91a70cca . _:0ae0983b-e875-e842-ca93-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0348 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Temperature" ; ph:dis "Bravo VAV 2-5 Zone Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e875-e843-ca94-f23c91a70cca . _:0ae0983b-e875-e843-ca94-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0349 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-50" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-50" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e875-e844-ca95-f23c91a70cca . _:0ae0983b-e875-e844-ca95-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-034a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-50 Damper Output" ; ph:dis "Bravo VAV 2-50 Damper Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e875-e845-ca96-f23c91a70cca . _:0ae0983b-e875-e845-ca96-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-034b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e875-e846-ca97-f23c91a70cca . _:0ae0983b-e875-e846-ca97-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-034c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e875-e847-ca98-f23c91a70cca . _:0ae0983b-e875-e847-ca98-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-034d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-50 Heating Valve Output" ; ph:dis "Bravo VAV 2-50 Heating Valve Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8a3-af00-ca99-f23c91a70cca . _:0ae0983b-e8a3-af00-ca99-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-034e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-50 Supply Air Temperature" ; ph:dis "Bravo VAV 2-50 Supply Air Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8a3-af01-ca9a-f23c91a70cca . _:0ae0983b-e8a3-af01-ca9a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-034f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-50 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8a3-af02-ca9b-f23c91a70cca . _:0ae0983b-e8a3-af02-ca9b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0350 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Temperature" ; ph:dis "Bravo VAV 2-50 Zone Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f140-ca9c-f23c91a70cca . _:0ae0983b-e8b2-f140-ca9c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0351 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-6" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8b2-f141-ca9d-f23c91a70cca . _:0ae0983b-e8b2-f141-ca9d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 350 . _:b-0352 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-6 Damper Output" ; ph:dis "Bravo VAV 2-6 Damper Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8b2-f142-ca9e-f23c91a70cca . _:0ae0983b-e8b2-f142-ca9e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0353 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8b2-f143-ca9f-f23c91a70cca . _:0ae0983b-e8b2-f143-ca9f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0354 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8b2-f144-caa0-f23c91a70cca . _:0ae0983b-e8b2-f144-caa0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0355 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-6 Heating Valve Output" ; ph:dis "Bravo VAV 2-6 Heating Valve Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8b2-f145-caa1-f23c91a70cca . _:0ae0983b-e8b2-f145-caa1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0356 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-6 Supply Air Temperature" ; ph:dis "Bravo VAV 2-6 Supply Air Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f146-caa2-f23c91a70cca . _:0ae0983b-e8b2-f146-caa2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0357 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f147-caa3-f23c91a70cca . _:0ae0983b-e8b2-f147-caa3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0358 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Temperature" ; ph:dis "Bravo VAV 2-6 Zone Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f148-caa4-f23c91a70cca . _:0ae0983b-e8b2-f148-caa4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0359 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-7" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8b2-f149-caa5-f23c91a70cca . _:0ae0983b-e8b2-f149-caa5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-035a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-7 Damper Output" ; ph:dis "Bravo VAV 2-7 Damper Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8b2-f14a-caa6-f23c91a70cca . _:0ae0983b-e8b2-f14a-caa6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-035b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8b2-f14b-caa7-f23c91a70cca . _:0ae0983b-e8b2-f14b-caa7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-035c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8b2-f14c-caa8-f23c91a70cca . _:0ae0983b-e8b2-f14c-caa8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-035d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-7 Heating Valve Output" ; ph:dis "Bravo VAV 2-7 Heating Valve Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8b2-f14d-caa9-f23c91a70cca . _:0ae0983b-e8b2-f14d-caa9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-035e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-7 Supply Air Temperature" ; ph:dis "Bravo VAV 2-7 Supply Air Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f14e-caaa-f23c91a70cca . _:0ae0983b-e8b2-f14e-caaa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-035f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f14f-caab-f23c91a70cca . _:0ae0983b-e8b2-f14f-caab-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0360 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Temperature" ; ph:dis "Bravo VAV 2-7 Zone Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8b2-f150-caac-f23c91a70cca . _:0ae0983b-e8b2-f150-caac-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0361 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-8" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8b2-f151-caad-f23c91a70cca . _:0ae0983b-e8b2-f151-caad-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0362 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-8 Damper Output" ; ph:dis "Bravo VAV 2-8 Damper Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8c2-3380-caae-f23c91a70cca . _:0ae0983b-e8c2-3380-caae-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0363 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-3381-caaf-f23c91a70cca . _:0ae0983b-e8c2-3381-caaf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0364 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-3382-cab0-f23c91a70cca . _:0ae0983b-e8c2-3382-cab0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0365 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-8 Heating Valve Output" ; ph:dis "Bravo VAV 2-8 Heating Valve Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8c2-3383-cab1-f23c91a70cca . _:0ae0983b-e8c2-3383-cab1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0366 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-8 Supply Air Temperature" ; ph:dis "Bravo VAV 2-8 Supply Air Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-3384-cab2-f23c91a70cca . _:0ae0983b-e8c2-3384-cab2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0367 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-3385-cab3-f23c91a70cca . _:0ae0983b-e8c2-3385-cab3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0368 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Temperature" ; ph:dis "Bravo VAV 2-8 Zone Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-3386-cab4-f23c91a70cca . _:0ae0983b-e8c2-3386-cab4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0369 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-9" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8c2-3387-cab5-f23c91a70cca . _:0ae0983b-e8c2-3387-cab5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-036a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-9 Damper Output" ; ph:dis "Bravo VAV 2-9 Damper Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8c2-3388-cab6-f23c91a70cca . _:0ae0983b-e8c2-3388-cab6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-036b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-3389-cab7-f23c91a70cca . _:0ae0983b-e8c2-3389-cab7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-036c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-338a-cab8-f23c91a70cca . _:0ae0983b-e8c2-338a-cab8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-036d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-9 Heating Valve Output" ; ph:dis "Bravo VAV 2-9 Heating Valve Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8c2-338b-cab9-f23c91a70cca . _:0ae0983b-e8c2-338b-cab9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-9 Supply Air Temperature" ; ph:dis "Bravo VAV 2-9 Supply Air Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-338c-caba-f23c91a70cca . _:0ae0983b-e8c2-338c-caba-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-338d-cabb-f23c91a70cca . _:0ae0983b-e8c2-338d-cabb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0370 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Temperature" ; ph:dis "Bravo VAV 2-9 Zone Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8c2-338e-cabc-f23c91a70cca . _:0ae0983b-e8c2-338e-cabc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0371 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-1" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8c2-338f-cabd-f23c91a70cca . _:0ae0983b-e8c2-338f-cabd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 14.1 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1300 . _:b-0372 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-1 Air Damper Command" ; ph:dis "Bravo VAV 3-1 Air Damper Command" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8c2-3390-cabe-f23c91a70cca . _:0ae0983b-e8c2-3390-cabe-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0373 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-3391-cabf-f23c91a70cca . _:0ae0983b-e8c2-3391-cabf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0374 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8c2-3392-cac0-f23c91a70cca . _:0ae0983b-e8c2-3392-cac0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0375 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-1 Heating Valve Output" ; ph:dis "Bravo VAV 3-1 Heating Valve Output" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8d1-75c0-cac1-f23c91a70cca . _:0ae0983b-e8d1-75c0-cac1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0376 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-1 Supply Air Temperature" ; ph:dis "Bravo VAV 3-1 Supply Air Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75c1-cac2-f23c91a70cca . _:0ae0983b-e8d1-75c1-cac2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0377 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75c2-cac3-f23c91a70cca . _:0ae0983b-e8d1-75c2-cac3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0378 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Temperature" ; ph:dis "Bravo VAV 3-1 Zone Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75c3-cac4-f23c91a70cca . _:0ae0983b-e8d1-75c3-cac4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0379 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-10" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8d1-75c4-cac5-f23c91a70cca . _:0ae0983b-e8d1-75c4-cac5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 7.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-037a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-10 Damper Output" ; ph:dis "Bravo VAV 3-10 Damper Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8d1-75c5-cac6-f23c91a70cca . _:0ae0983b-e8d1-75c5-cac6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-037b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8d1-75c6-cac7-f23c91a70cca . _:0ae0983b-e8d1-75c6-cac7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-037c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8d1-75c7-cac8-f23c91a70cca . _:0ae0983b-e8d1-75c7-cac8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-037d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-10 Heating Valve Output" ; ph:dis "Bravo VAV 3-10 Heating Valve Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8d1-75c8-cac9-f23c91a70cca . _:0ae0983b-e8d1-75c8-cac9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-037e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-10 Supply Air Temperature" ; ph:dis "Bravo VAV 3-10 Supply Air Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75c9-caca-f23c91a70cca . _:0ae0983b-e8d1-75c9-caca-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-037f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75ca-cacb-f23c91a70cca . _:0ae0983b-e8d1-75ca-cacb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0380 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Temperature" ; ph:dis "Bravo VAV 3-10 Zone Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75cb-cacc-f23c91a70cca . _:0ae0983b-e8d1-75cb-cacc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0381 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-11" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8d1-75cc-cacd-f23c91a70cca . _:0ae0983b-e8d1-75cc-cacd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 22.7 ; _:designHotWaterFlow 2.25 ; _:designAirFlow 1100 . _:b-0382 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-11 Damper Output" ; ph:dis "Bravo VAV 3-11 Damper Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8d1-75cd-cace-f23c91a70cca . _:0ae0983b-e8d1-75cd-cace-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0383 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8d1-75ce-cacf-f23c91a70cca . _:0ae0983b-e8d1-75ce-cacf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0384 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e8d1-75cf-cad0-f23c91a70cca . _:0ae0983b-e8d1-75cf-cad0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0385 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-11 Heating Valve Output" ; ph:dis "Bravo VAV 3-11 Heating Valve Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e8d1-75d0-cad1-f23c91a70cca . _:0ae0983b-e8d1-75d0-cad1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0386 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-11 Supply Air Temperature" ; ph:dis "Bravo VAV 3-11 Supply Air Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75d1-cad2-f23c91a70cca . _:0ae0983b-e8d1-75d1-cad2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0387 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8d1-75d2-cad3-f23c91a70cca . _:0ae0983b-e8d1-75d2-cad3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0388 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Temperature" ; ph:dis "Bravo VAV 3-11 Zone Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e8e0-b800-cad4-f23c91a70cca . _:0ae0983b-e8e0-b800-cad4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0389 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-12" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e8e0-b801-cad5-f23c91a70cca . _:0ae0983b-e8e0-b801-cad5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 1000 . _:b-038a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-12 Damper Output" ; ph:dis "Bravo VAV 3-12 Damper Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e90e-7ec0-cad6-f23c91a70cca . _:0ae0983b-e90e-7ec0-cad6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-038b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e90e-7ec1-cad7-f23c91a70cca . _:0ae0983b-e90e-7ec1-cad7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-038c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e90e-7ec2-cad8-f23c91a70cca . _:0ae0983b-e90e-7ec2-cad8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-038d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-12 Heating Valve Output" ; ph:dis "Bravo VAV 3-12 Heating Valve Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e90e-7ec3-cad9-f23c91a70cca . _:0ae0983b-e90e-7ec3-cad9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-038e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-12 Supply Air Temperature" ; ph:dis "Bravo VAV 3-12 Supply Air Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e90e-7ec4-cada-f23c91a70cca . _:0ae0983b-e90e-7ec4-cada-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-038f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e90e-7ec5-cadb-f23c91a70cca . _:0ae0983b-e90e-7ec5-cadb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0390 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Temperature" ; ph:dis "Bravo VAV 3-12 Zone Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e90e-7ec6-cadc-f23c91a70cca . _:0ae0983b-e90e-7ec6-cadc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0391 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-13" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e90e-7ec7-cadd-f23c91a70cca . _:0ae0983b-e90e-7ec7-cadd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 5.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0392 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-13 Damper Output" ; ph:dis "Bravo VAV 3-13 Damper Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e90e-7ec8-cade-f23c91a70cca . _:0ae0983b-e90e-7ec8-cade-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0393 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c100-cadf-f23c91a70cca . _:0ae0983b-e91d-c100-cadf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0394 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c101-cae0-f23c91a70cca . _:0ae0983b-e91d-c101-cae0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0395 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-13 Heating Valve Output" ; ph:dis "Bravo VAV 3-13 Heating Valve Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e91d-c102-cae1-f23c91a70cca . _:0ae0983b-e91d-c102-cae1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0396 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-13 Supply Air Temperature" ; ph:dis "Bravo VAV 3-13 Supply Air Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c103-cae2-f23c91a70cca . _:0ae0983b-e91d-c103-cae2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0397 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c104-cae3-f23c91a70cca . _:0ae0983b-e91d-c104-cae3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0398 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Temperature" ; ph:dis "Bravo VAV 3-13 Zone Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c105-cae4-f23c91a70cca . _:0ae0983b-e91d-c105-cae4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0399 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-14" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e91d-c106-cae5-f23c91a70cca . _:0ae0983b-e91d-c106-cae5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 5.4 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-039a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-14 Damper Output" ; ph:dis "Bravo VAV 3-14 Damper Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e91d-c107-cae6-f23c91a70cca . _:0ae0983b-e91d-c107-cae6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-039b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c108-cae7-f23c91a70cca . _:0ae0983b-e91d-c108-cae7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-039c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c109-cae8-f23c91a70cca . _:0ae0983b-e91d-c109-cae8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-039d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-14 Heating Valve Output" ; ph:dis "Bravo VAV 3-14 Heating Valve Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e91d-c10a-cae9-f23c91a70cca . _:0ae0983b-e91d-c10a-cae9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-039e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-14 Supply Air Temperature" ; ph:dis "Bravo VAV 3-14 Supply Air Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c10b-caea-f23c91a70cca . _:0ae0983b-e91d-c10b-caea-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-039f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c10c-caeb-f23c91a70cca . _:0ae0983b-e91d-c10c-caeb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Temperature" ; ph:dis "Bravo VAV 3-14 Zone Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e91d-c10d-caec-f23c91a70cca . _:0ae0983b-e91d-c10d-caec-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-15" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e91d-c10e-caed-f23c91a70cca . _:0ae0983b-e91d-c10e-caed-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 147 ; _:designHotWaterPower 2.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-03a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-15 Damper Output" ; ph:dis "Bravo VAV 3-15 Damper Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e91d-c10f-caee-f23c91a70cca . _:0ae0983b-e91d-c10f-caee-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c110-caef-f23c91a70cca . _:0ae0983b-e91d-c110-caef-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e91d-c111-caf0-f23c91a70cca . _:0ae0983b-e91d-c111-caf0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-15 Heating Valve Output" ; ph:dis "Bravo VAV 3-15 Heating Valve Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e91d-c112-caf1-f23c91a70cca . _:0ae0983b-e91d-c112-caf1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-15 Supply Air Temperature" ; ph:dis "Bravo VAV 3-15 Supply Air Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0340-caf2-f23c91a70cca . _:0ae0983b-e92d-0340-caf2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0341-caf3-f23c91a70cca . _:0ae0983b-e92d-0341-caf3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Temperature" ; ph:dis "Bravo VAV 3-15 Zone Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0342-caf4-f23c91a70cca . _:0ae0983b-e92d-0342-caf4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-16" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e92d-0343-caf5-f23c91a70cca . _:0ae0983b-e92d-0343-caf5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-16 Damper Output" ; ph:dis "Bravo VAV 3-16 Damper Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e92d-0344-caf6-f23c91a70cca . _:0ae0983b-e92d-0344-caf6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e92d-0345-caf7-f23c91a70cca . _:0ae0983b-e92d-0345-caf7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e92d-0346-caf8-f23c91a70cca . _:0ae0983b-e92d-0346-caf8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-16 Heating Valve Output" ; ph:dis "Bravo VAV 3-16 Heating Valve Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e92d-0347-caf9-f23c91a70cca . _:0ae0983b-e92d-0347-caf9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-16 Supply Air Temperature" ; ph:dis "Bravo VAV 3-16 Supply Air Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0348-cafa-f23c91a70cca . _:0ae0983b-e92d-0348-cafa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0349-cafb-f23c91a70cca . _:0ae0983b-e92d-0349-cafb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Temperature" ; ph:dis "Bravo VAV 3-16 Zone Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-034a-cafc-f23c91a70cca . _:0ae0983b-e92d-034a-cafc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-17" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e92d-034b-cafd-f23c91a70cca . _:0ae0983b-e92d-034b-cafd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-17 Damper Output" ; ph:dis "Bravo VAV 3-17 Damper Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e92d-034c-cafe-f23c91a70cca . _:0ae0983b-e92d-034c-cafe-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e92d-034d-caff-f23c91a70cca . _:0ae0983b-e92d-034d-caff-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e92d-034e-cb00-f23c91a70cca . _:0ae0983b-e92d-034e-cb00-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-17 Heating Valve Output" ; ph:dis "Bravo VAV 3-17 Heating Valve Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e92d-034f-cb01-f23c91a70cca . _:0ae0983b-e92d-034f-cb01-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-17 Supply Air Temperature" ; ph:dis "Bravo VAV 3-17 Supply Air Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0350-cb02-f23c91a70cca . _:0ae0983b-e92d-0350-cb02-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0351-cb03-f23c91a70cca . _:0ae0983b-e92d-0351-cb03-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Temperature" ; ph:dis "Bravo VAV 3-17 Zone Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e92d-0352-cb04-f23c91a70cca . _:0ae0983b-e92d-0352-cb04-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-18" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e93c-4580-cb05-f23c91a70cca . _:0ae0983b-e93c-4580-cb05-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 12.4 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 500 . _:b-03ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-18 Damper Output" ; ph:dis "Bravo VAV 3-18 Damper Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e93c-4581-cb06-f23c91a70cca . _:0ae0983b-e93c-4581-cb06-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e93c-4582-cb07-f23c91a70cca . _:0ae0983b-e93c-4582-cb07-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e93c-4583-cb08-f23c91a70cca . _:0ae0983b-e93c-4583-cb08-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-18 Heating Valve Output" ; ph:dis "Bravo VAV 3-18 Heating Valve Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e93c-4584-cb09-f23c91a70cca . _:0ae0983b-e93c-4584-cb09-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-18 Supply Air Temperature" ; ph:dis "Bravo VAV 3-18 Supply Air Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e93c-4585-cb0a-f23c91a70cca . _:0ae0983b-e93c-4585-cb0a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e93c-4586-cb0b-f23c91a70cca . _:0ae0983b-e93c-4586-cb0b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Temperature" ; ph:dis "Bravo VAV 3-18 Zone Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e93c-4587-cb0c-f23c91a70cca . _:0ae0983b-e93c-4587-cb0c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-19" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e93c-4588-cb0d-f23c91a70cca . _:0ae0983b-e93c-4588-cb0d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 2.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-03c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-19 Damper Output" ; ph:dis "Bravo VAV 3-19 Damper Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e93c-4589-cb0e-f23c91a70cca . _:0ae0983b-e93c-4589-cb0e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e93c-458a-cb0f-f23c91a70cca . _:0ae0983b-e93c-458a-cb0f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e93c-458b-cb10-f23c91a70cca . _:0ae0983b-e93c-458b-cb10-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-19 Heating Valve Output" ; ph:dis "Bravo VAV 3-19 Heating Valve Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e93c-458c-cb11-f23c91a70cca . _:0ae0983b-e93c-458c-cb11-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-19 Supply Air Temperature" ; ph:dis "Bravo VAV 3-19 Supply Air Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e979-4e80-cb12-f23c91a70cca . _:0ae0983b-e979-4e80-cb12-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e979-4e81-cb13-f23c91a70cca . _:0ae0983b-e979-4e81-cb13-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Temperature" ; ph:dis "Bravo VAV 3-19 Zone Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d300-cb14-f23c91a70cca . _:0ae0983b-e997-d300-cb14-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-2" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e997-d301-cb15-f23c91a70cca . _:0ae0983b-e997-d301-cb15-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.7 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 800 . _:b-03ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-2 Damper Output" ; ph:dis "Bravo VAV 3-2 Damper Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e997-d302-cb16-f23c91a70cca . _:0ae0983b-e997-d302-cb16-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e997-d303-cb17-f23c91a70cca . _:0ae0983b-e997-d303-cb17-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e997-d304-cb18-f23c91a70cca . _:0ae0983b-e997-d304-cb18-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-2 Heating Valve Output" ; ph:dis "Bravo VAV 3-2 Heating Valve Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e997-d305-cb19-f23c91a70cca . _:0ae0983b-e997-d305-cb19-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-2 Supply Air Temperature" ; ph:dis "Bravo VAV 3-2 Supply Air Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d306-cb1a-f23c91a70cca . _:0ae0983b-e997-d306-cb1a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d307-cb1b-f23c91a70cca . _:0ae0983b-e997-d307-cb1b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Temperature" ; ph:dis "Bravo VAV 3-2 Zone Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d308-cb1c-f23c91a70cca . _:0ae0983b-e997-d308-cb1c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-20" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e997-d309-cb1d-f23c91a70cca . _:0ae0983b-e997-d309-cb1d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-20 Damper Output" ; ph:dis "Bravo VAV 3-20 Damper Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e997-d30a-cb1e-f23c91a70cca . _:0ae0983b-e997-d30a-cb1e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e997-d30b-cb1f-f23c91a70cca . _:0ae0983b-e997-d30b-cb1f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e997-d30c-cb20-f23c91a70cca . _:0ae0983b-e997-d30c-cb20-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-20 Heating Valve Output" ; ph:dis "Bravo VAV 3-20 Heating Valve Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e997-d30d-cb21-f23c91a70cca . _:0ae0983b-e997-d30d-cb21-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-20 Supply Air Temperature" ; ph:dis "Bravo VAV 3-20 Supply Air Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d30e-cb22-f23c91a70cca . _:0ae0983b-e997-d30e-cb22-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e997-d30f-cb23-f23c91a70cca . _:0ae0983b-e997-d30f-cb23-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Temperature" ; ph:dis "Bravo VAV 3-20 Zone Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9a7-1540-cb24-f23c91a70cca . _:0ae0983b-e9a7-1540-cb24-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-21" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9a7-1541-cb25-f23c91a70cca . _:0ae0983b-e9a7-1541-cb25-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-03da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-21 Damper Output" ; ph:dis "Bravo VAV 3-21 Damper Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9a7-1542-cb26-f23c91a70cca . _:0ae0983b-e9a7-1542-cb26-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-03db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9a7-1543-cb27-f23c91a70cca . _:0ae0983b-e9a7-1543-cb27-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9a7-1544-cb28-f23c91a70cca . _:0ae0983b-e9a7-1544-cb28-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-21 Heating Valve Output" ; ph:dis "Bravo VAV 3-21 Heating Valve Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9a7-1545-cb29-f23c91a70cca . _:0ae0983b-e9a7-1545-cb29-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-21 Supply Air Temperature" ; ph:dis "Bravo VAV 3-21 Supply Air Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9a7-1546-cb2a-f23c91a70cca . _:0ae0983b-e9a7-1546-cb2a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9a7-1547-cb2b-f23c91a70cca . _:0ae0983b-e9a7-1547-cb2b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Temperature" ; ph:dis "Bravo VAV 3-21 Zone Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9a7-1548-cb2c-f23c91a70cca . _:0ae0983b-e9a7-1548-cb2c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-22" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9d4-dc00-cb2d-f23c91a70cca . _:0ae0983b-e9d4-dc00-cb2d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 29.2 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 1250 . _:b-03e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-22 Damper Output" ; ph:dis "Bravo VAV 3-22 Damper Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9d4-dc01-cb2e-f23c91a70cca . _:0ae0983b-e9d4-dc01-cb2e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9e4-1e40-cb2f-f23c91a70cca . _:0ae0983b-e9e4-1e40-cb2f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9e4-1e41-cb30-f23c91a70cca . _:0ae0983b-e9e4-1e41-cb30-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-22 Heating Valve Output" ; ph:dis "Bravo VAV 3-22 Heating Valve Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9e4-1e42-cb31-f23c91a70cca . _:0ae0983b-e9e4-1e42-cb31-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-22 Supply Air Temperature" ; ph:dis "Bravo VAV 3-22 Supply Air Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e43-cb32-f23c91a70cca . _:0ae0983b-e9e4-1e43-cb32-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e44-cb33-f23c91a70cca . _:0ae0983b-e9e4-1e44-cb33-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Temperature" ; ph:dis "Bravo VAV 3-22 Zone Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e45-cb34-f23c91a70cca . _:0ae0983b-e9e4-1e45-cb34-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-23" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9e4-1e46-cb35-f23c91a70cca . _:0ae0983b-e9e4-1e46-cb35-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-03ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-23 Damper Output" ; ph:dis "Bravo VAV 3-23 Damper Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9e4-1e47-cb36-f23c91a70cca . _:0ae0983b-e9e4-1e47-cb36-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-03eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9e4-1e48-cb37-f23c91a70cca . _:0ae0983b-e9e4-1e48-cb37-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9e4-1e49-cb38-f23c91a70cca . _:0ae0983b-e9e4-1e49-cb38-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-23 Heating Valve Output" ; ph:dis "Bravo VAV 3-23 Heating Valve Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9e4-1e4a-cb39-f23c91a70cca . _:0ae0983b-e9e4-1e4a-cb39-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-23 Supply Air Temperature" ; ph:dis "Bravo VAV 3-23 Supply Air Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e4b-cb3a-f23c91a70cca . _:0ae0983b-e9e4-1e4b-cb3a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e4c-cb3b-f23c91a70cca . _:0ae0983b-e9e4-1e4c-cb3b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Temperature" ; ph:dis "Bravo VAV 3-23 Zone Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9e4-1e4d-cb3c-f23c91a70cca . _:0ae0983b-e9e4-1e4d-cb3c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-24" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9e4-1e4e-cb3d-f23c91a70cca . _:0ae0983b-e9e4-1e4e-cb3d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-24 Damper Output" ; ph:dis "Bravo VAV 3-24 Damper Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9f3-6080-cb3e-f23c91a70cca . _:0ae0983b-e9f3-6080-cb3e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9f3-6081-cb3f-f23c91a70cca . _:0ae0983b-e9f3-6081-cb3f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9f3-6082-cb40-f23c91a70cca . _:0ae0983b-e9f3-6082-cb40-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-24 Heating Valve Output" ; ph:dis "Bravo VAV 3-24 Heating Valve Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9f3-6083-cb41-f23c91a70cca . _:0ae0983b-e9f3-6083-cb41-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-24 Supply Air Temperature" ; ph:dis "Bravo VAV 3-24 Supply Air Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-6084-cb42-f23c91a70cca . _:0ae0983b-e9f3-6084-cb42-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-6085-cb43-f23c91a70cca . _:0ae0983b-e9f3-6085-cb43-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Temperature" ; ph:dis "Bravo VAV 3-24 Zone Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-6086-cb44-f23c91a70cca . _:0ae0983b-e9f3-6086-cb44-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-25" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9f3-6087-cb45-f23c91a70cca . _:0ae0983b-e9f3-6087-cb45-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 16.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-03fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-25 Damper Output" ; ph:dis "Bravo VAV 3-25 Damper Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9f3-6088-cb46-f23c91a70cca . _:0ae0983b-e9f3-6088-cb46-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9f3-6089-cb47-f23c91a70cca . _:0ae0983b-e9f3-6089-cb47-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-e9f3-608a-cb48-f23c91a70cca . _:0ae0983b-e9f3-608a-cb48-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-25 Heating Valve Output" ; ph:dis "Bravo VAV 3-25 Heating Valve Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-e9f3-608b-cb49-f23c91a70cca . _:0ae0983b-e9f3-608b-cb49-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-25 Supply Air Temperature" ; ph:dis "Bravo VAV 3-25 Supply Air Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-608c-cb4a-f23c91a70cca . _:0ae0983b-e9f3-608c-cb4a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-608d-cb4b-f23c91a70cca . _:0ae0983b-e9f3-608d-cb4b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0400 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Temperature" ; ph:dis "Bravo VAV 3-25 Zone Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-e9f3-608e-cb4c-f23c91a70cca . _:0ae0983b-e9f3-608e-cb4c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0401 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-26" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-e9f3-608f-cb4d-f23c91a70cca . _:0ae0983b-e9f3-608f-cb4d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 12.9 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 400 . _:b-0402 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-26 Damper Output" ; ph:dis "Bravo VAV 3-26 Damper Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea02-a2c0-cb4e-f23c91a70cca . _:0ae0983b-ea02-a2c0-cb4e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0403 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2c1-cb4f-f23c91a70cca . _:0ae0983b-ea02-a2c1-cb4f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0404 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2c2-cb50-f23c91a70cca . _:0ae0983b-ea02-a2c2-cb50-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0405 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-26 Heating Valve Output" ; ph:dis "Bravo VAV 3-26 Heating Valve Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea02-a2c3-cb51-f23c91a70cca . _:0ae0983b-ea02-a2c3-cb51-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0406 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-26 Supply Air Temperature" ; ph:dis "Bravo VAV 3-26 Supply Air Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2c4-cb52-f23c91a70cca . _:0ae0983b-ea02-a2c4-cb52-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0407 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2c5-cb53-f23c91a70cca . _:0ae0983b-ea02-a2c5-cb53-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0408 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Temperature" ; ph:dis "Bravo VAV 3-26 Zone Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2c6-cb54-f23c91a70cca . _:0ae0983b-ea02-a2c6-cb54-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0409 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-27" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea02-a2c7-cb55-f23c91a70cca . _:0ae0983b-ea02-a2c7-cb55-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-040a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-27 Damper Output" ; ph:dis "Bravo VAV 3-27 Damper Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea02-a2c8-cb56-f23c91a70cca . _:0ae0983b-ea02-a2c8-cb56-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-040b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2c9-cb57-f23c91a70cca . _:0ae0983b-ea02-a2c9-cb57-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-040c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2ca-cb58-f23c91a70cca . _:0ae0983b-ea02-a2ca-cb58-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-040d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-27 Heating Valve Output" ; ph:dis "Bravo VAV 3-27 Heating Valve Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea02-a2cb-cb59-f23c91a70cca . _:0ae0983b-ea02-a2cb-cb59-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-040e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-27 Supply Air Temperature" ; ph:dis "Bravo VAV 3-27 Supply Air Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2cc-cb5a-f23c91a70cca . _:0ae0983b-ea02-a2cc-cb5a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime ; _:pointType "" . _:b-040f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2cd-cb5b-f23c91a70cca . _:0ae0983b-ea02-a2cd-cb5b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0410 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Temperature" ; ph:dis "Bravo VAV 3-27 Zone Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea02-a2ce-cb5c-f23c91a70cca . _:0ae0983b-ea02-a2ce-cb5c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0411 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-28" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea02-a2cf-cb5d-f23c91a70cca . _:0ae0983b-ea02-a2cf-cb5d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0412 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-28 Damper Output" ; ph:dis "Bravo VAV 3-28 Damper Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea02-a2d0-cb5e-f23c91a70cca . _:0ae0983b-ea02-a2d0-cb5e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0413 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2d1-cb5f-f23c91a70cca . _:0ae0983b-ea02-a2d1-cb5f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0414 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea02-a2d2-cb60-f23c91a70cca . _:0ae0983b-ea02-a2d2-cb60-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0415 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-28 Heating Valve Output" ; ph:dis "Bravo VAV 3-28 Heating Valve Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0ae0983b-ea11-e500-cb61-f23c91a70cca . _:0ae0983b-ea11-e500-cb61-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0416 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-28 Supply Air Temperature" ; ph:dis "Bravo VAV 3-28 Supply Air Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea11-e501-cb62-f23c91a70cca . _:0ae0983b-ea11-e501-cb62-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0417 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea3f-abc0-cb63-f23c91a70cca . _:0ae0983b-ea3f-abc0-cb63-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0418 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Temperature" ; ph:dis "Bravo VAV 3-28 Zone Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0ae0983b-ea3f-abc1-cb64-f23c91a70cca . _:0ae0983b-ea3f-abc1-cb64-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0419 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-3" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea3f-abc2-cb65-f23c91a70cca . _:0ae0983b-ea3f-abc2-cb65-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-041a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-3 Supply Air Flow" ; ph:dis "Bravo VAV 3-3 Supply Air Flow" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea3f-abc3-cb66-f23c91a70cca . _:0ae0983b-ea3f-abc3-cb66-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-041b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-3 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-3 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea3f-abc4-cb67-f23c91a70cca . _:0ae0983b-ea3f-abc4-cb67-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-041c a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-4" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea3f-abc5-cb68-f23c91a70cca . _:0ae0983b-ea3f-abc5-cb68-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 1.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-041d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-4 Supply Air Flow" ; ph:dis "Bravo VAV 3-4 Supply Air Flow" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea3f-abc6-cb69-f23c91a70cca . _:0ae0983b-ea3f-abc6-cb69-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-041e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-4 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-4 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea3f-abc7-cb6a-f23c91a70cca . _:0ae0983b-ea3f-abc7-cb6a-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-041f a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-5" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea4e-ee00-cb6b-f23c91a70cca . _:0ae0983b-ea4e-ee00-cb6b-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0420 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-5 Supply Air Flow" ; ph:dis "Bravo VAV 3-5 Supply Air Flow" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee01-cb6c-f23c91a70cca . _:0ae0983b-ea4e-ee01-cb6c-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0421 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-5 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-5 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee02-cb6d-f23c91a70cca . _:0ae0983b-ea4e-ee02-cb6d-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0422 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-6" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea4e-ee03-cb6e-f23c91a70cca . _:0ae0983b-ea4e-ee03-cb6e-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 600 . _:b-0423 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-6 Supply Air Flow" ; ph:dis "Bravo VAV 3-6 Supply Air Flow" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee04-cb6f-f23c91a70cca . _:0ae0983b-ea4e-ee04-cb6f-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0424 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-6 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-6 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee05-cb70-f23c91a70cca . _:0ae0983b-ea4e-ee05-cb70-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0425 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-7" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea4e-ee06-cb71-f23c91a70cca . _:0ae0983b-ea4e-ee06-cb71-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 700 . _:b-0426 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-7 Supply Air Flow" ; ph:dis "Bravo VAV 3-7 Supply Air Flow" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee07-cb72-f23c91a70cca . _:0ae0983b-ea4e-ee07-cb72-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0427 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-7 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-7 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee08-cb73-f23c91a70cca . _:0ae0983b-ea4e-ee08-cb73-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0428 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-8" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea4e-ee09-cb74-f23c91a70cca . _:0ae0983b-ea4e-ee09-cb74-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0429 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-8 Supply Air Flow" ; ph:dis "Bravo VAV 3-8 Supply Air Flow" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee0a-cb75-f23c91a70cca . _:0ae0983b-ea4e-ee0a-cb75-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-042a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-8 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-8 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee0b-cb76-f23c91a70cca . _:0ae0983b-ea4e-ee0b-cb76-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-042b a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-9" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0ae0983b-ea4e-ee0c-cb77-f23c91a70cca . _:0ae0983b-ea4e-ee0c-cb77-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 23 ; _:designHotWaterFlow 4 ; _:designAirFlow 2000 . _:b-042c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-9 Supply Air Flow" ; ph:dis "Bravo VAV 3-9 Supply Air Flow" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee0d-cb78-f23c91a70cca . _:0ae0983b-ea4e-ee0d-cb78-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-042d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-9 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-9 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0ae0983b-ea4e-ee0e-cb79-f23c91a70cca . _:0ae0983b-ea4e-ee0e-cb79-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-042e a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo VAVs" ; ph:dis "Bravo VAVs" ; phIoT:siteRef _:b-0000 ; _:custom _:0ae0983b-ea4e-ee0f-cb7a-f23c91a70cca . _:0ae0983b-ea4e-ee0f-cb7a-f23c91a70cca rdfs:label "" . _:b-042f a phIoT:weatherStation ; ph:hasTag phIoT:weatherStation ; rdfs:label "Fort Wayne, IN" ; ph:dis "Fort Wayne, IN" ; ph:geoCity "Fort Wayne" ; ph:geoCoord "C(41.131,-85.129)"^^ph:coord ; ph:geoCountry "US" ; ph:geoState "IN" ; ph:tz "Indianapolis" . _:b-0430 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor, phScience:weather, phScience:weatherCond ; rdfs:label "Fort Wayne, IN Condition" ; ph:dis "Fort Wayne, IN Condition" ; ph:enum "unknown,clear,partlyCloudy,cloudy,showers,rain,thunderstorms,ice,flurries,snow" ; ph:kind "Str" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0431 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Humidity" ; ph:dis "Fort Wayne, IN Humidity" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "%RH" ; phIoT:weatherStationRef _:b-042f . _:b-0432 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:daytime, phIoT:his, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Sunrise" ; ph:dis "Fort Wayne, IN Sunrise" ; ph:kind "Bool" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0433 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:weather ; rdfs:label "Fort Wayne, IN Temp" ; ph:dis "Fort Wayne, IN Temp" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "\u00b0F" ; phIoT:weatherStationRef _:b-042f . _:b-0434 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Points Not Syncing" ; ph:dis "Points Not Syncing" ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0ae0983b-ea5e-3040-cb7b-f23c91a70cca . _:0ae0983b-ea5e-3040-cb7b-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime .